Plan Review Notes For Permit 02071609 |
Permit Number |
02071609 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-13 00:00:00 | DENIED: | | | | 1. THE "SYSTEM SIZING SUMMARY" INDICATES | | SYSTEMS 1A, 2 & 3.PLAN INDICATES | | SYSTEMS 1A & B, 2A, B, & C, AND 3. | | PLEASE PROVIDE SCHEDULE FOR THE RTU | | EQUIPMENT. | | | | 2. PLEASE PROVIDE OUTSIDE AIR CALCS AS | | PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | 62-89. | | | | 3. RETURN AIR DUCTS & GRILLES ARE NOT | | SIZED. | | | | 4. AREA SERVED BY RTU #3 APPEARS TO HAVE | | A RETURN AIR PLENUM. PLEASE NOTE | | AS PER 2001 FBC(M) 602.2.1, MATERIALS | | EXPOSED WITHIN PLENUMS SHALL BE NON- | | COMBUSTIBLE OR SHALL HAVE A FLAME | | SPREAD INDEX IF NOT MORE THAN 25 & A | | SMOKE-DEVELOPED INDEX OF NOT MORE | | THAN 50 WHEN TESTED IN ACCORDANCE | | WITH ASTM E 84. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|