Plan Review Notes
Plan Review Notes For Permit 02071609
Permit Number 02071609
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-02 00:00:001) PLEASE INDICATE ON THE PLANS WHERE
 THE TENANT DEMISING WALLS ARE LOCATED.
  
 2) PLANS DO INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) IT APPEARS THAT NOT ENOUGH
 ILLUMINATED EXIT SIGNS OR EMERGENCY
 LIGHTING EQUIPMENT ARE PRESENT WITHIN
 THE SPACE.
  
 4) SOME DEAD-ENDS EXIST THAT MAY EXCEED
 BUILDING CODE REQUIREMENTS.
  
 5) ROOMS SHOULD BE LABELED ON THE
 FLOOR PLAN.
  
 6) NO MENTION OF FIRE SPRINKLERS, FIRE
 ALARM OR FIRE EXTINGUISHER EQUIPMENT
 WITHIN THE TENANT SPACE. PLEASE ADVISE
 AND REVISE AS NECESSARY.
  
 7) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS.
  
 8) PLEASE PROVIDE MORE INFORMATION ON
 ELECTRONIC LATCHES. SECURITY DEVICES
 SHALL NOT INTERFERE WITH ANY EXITING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910