Plan Review Notes For Permit 02071609 |
Permit Number |
02071609 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-02 00:00:00 | 1) PLEASE INDICATE ON THE PLANS WHERE | | THE TENANT DEMISING WALLS ARE LOCATED. | | | | 2) PLANS DO INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 3) IT APPEARS THAT NOT ENOUGH | | ILLUMINATED EXIT SIGNS OR EMERGENCY | | LIGHTING EQUIPMENT ARE PRESENT WITHIN | | THE SPACE. | | | | 4) SOME DEAD-ENDS EXIST THAT MAY EXCEED | | BUILDING CODE REQUIREMENTS. | | | | 5) ROOMS SHOULD BE LABELED ON THE | | FLOOR PLAN. | | | | 6) NO MENTION OF FIRE SPRINKLERS, FIRE | | ALARM OR FIRE EXTINGUISHER EQUIPMENT | | WITHIN THE TENANT SPACE. PLEASE ADVISE | | AND REVISE AS NECESSARY. | | | | 7) PLEASE PROVIDE OCCUPANT LOAD | | CALCULATIONS. | | | | 8) PLEASE PROVIDE MORE INFORMATION ON | | ELECTRONIC LATCHES. SECURITY DEVICES | | SHALL NOT INTERFERE WITH ANY EXITING. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|