Date |
Text |
2002-08-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT:02071609 |
| ADD:1400 NORTHPOINT |
| CONT: LTI DEVELOPMENT |
| TEL: (561)478-1841 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) INDICATE BUILDING TYPE, PROTECTED OR |
| NON-PROTECTED, FIRE SPRINKLERED? TABLE |
| 500 / OCCUPANCY VS SQ FT? |
| |
| 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 3) SHEET A-1.1 1 HR DIMISSING WALL DE- |
| TAIL, DRYWALL NOR TRACK GO ALL THE WAY |
| TO THE ROOF DECK. 705.6 |
| |
| 4) 705.7.1 FIRE RESISTANT JOINT SYSTEMS |
| THE JOINT LEFT BETWEEN THE WALL AND |
| THE FLOOR/CEILING ASSEMBLY OR CEILING/ |
| ROOF ASSEMBLY SHALL BE PROTECTED BY AN |
| APPROVED FIRE RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE |
| FOR A TIME PERIOD NOT LESS THAN REQUIRED |
| FOR THE WALL. |
| |
| 5) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 6) 1005.2 DEAD END POCKETS. EXIT ACCESS |
| SHALL BE SO ARRANGED THAT DEAD END POC- |
| KETS OR HALLWAYS IN EXCESS OF 20 FT LONG |
| SHALL NOT OCCUR. |
| |
| 7) PROVIDE ADDITIONAL INFORMATION ON |
| ELECTRIC LOCKING MECHANISMS, 1012.6.1. |
| PROVIDE MANUFACTURERS SPEC. |
| |
| 8) PROVIDE ROOM USAGE, PLEASE INDICATE |
| ON FLOOR PLAN. |
| |
| 9)11-4.1.3(3) GROUND & FLOOR SURFACES |
| ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| ROOMS & SPACES SHALL COMPLY WITH |
| 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| IS RECOMENDED FOR ACCESSIBLE ROUTES |
| AND 0.8 FOR RAMPS. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |