Plan Review Notes For Permit 02071604 |
Permit Number |
02071604 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT A-103 ROOF DRAINS CHANGED ON ROOF | | OF SERVICE DRIVE, (WEST SIDE). SHOW | | SLOPE OF ROOF TO DRAINS. SECONDARY ROOF | | DRAINS NOT SHOWN. SHOW LOCATION, SIZE | | ECT. 104.2.1 | | 2) SHT P-101 SECONDARY ROOF DRAINS, | | (OVERFLOW DRAINS) REMOVED. DRAINS REQ- | | UIRED PER SECTION 1107. | | 3) SHT P-101 SUBMIT A STORM RISER DIA- | | GRAM. SHOW ALL PIPE SIZES, SLOPE OF PIPE | | AND SQUARE FOOTAGE AS IT ACCUMULATES IN | | SYSTEM ECT. | | 4) SHT P-301 WATER RISER DIAGRAM, A | | PROVISO WAS ISSUED AT TIME OF PERMIT FOR | | WATER HAMMER ARRESTOR LOCATION 8-12-2. | | THIS PROVISO SHALL BE CORRECTED ON THIS | | REVISION. WATER HAMMER ARRESTORS SHALL | | BE LOCATED PER PDI-WH201 AND MANUF. IN- | | STALLATION INSTRUCTIONS, NOT IN CEILING. | | 5) SHT A-103 SUBMIT CALCULATIONS FOR | | PRIMARY AND SECONDARY DRAINS FOR THE | | LOWER ROOFS. SHOW 1/2 AREA OF ALL VERTI- | | CAL WALLS AND SHOW ALL AREAS OF ROOFS | | THAT DRAIN ON TO LOWER ROOF FROM ABOVE. | | SECTIONS 1106, 1106.2, 1106.3, 1106.4, | | 1106.5, 1106.6, 1107, 1107.1, 1107.2, | | AND 1107.3 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|