2003-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-103 ROOF DRAINS CHANGED ON ROOF
 OF SERVICE DRIVE, (WEST SIDE). SHOW
 SLOPE OF ROOF TO DRAINS. SECONDARY ROOF
 DRAINS NOT SHOWN. SHOW LOCATION, SIZE
 ECT. 104.2.1
 2) SHT P-101 SECONDARY ROOF DRAINS,
 (OVERFLOW DRAINS) REMOVED. DRAINS REQ-
 UIRED PER SECTION 1107.
 3) SHT P-101 SUBMIT A STORM RISER DIA-
 GRAM. SHOW ALL PIPE SIZES, SLOPE OF PIPE
 AND SQUARE FOOTAGE AS IT ACCUMULATES IN
 SYSTEM ECT.
 4) SHT P-301 WATER RISER DIAGRAM, A
 PROVISO WAS ISSUED AT TIME OF PERMIT FOR
 WATER HAMMER ARRESTOR LOCATION 8-12-2.
 THIS PROVISO SHALL BE CORRECTED ON THIS
 REVISION. WATER HAMMER ARRESTORS SHALL
 BE LOCATED PER PDI-WH201 AND MANUF. IN-
 STALLATION INSTRUCTIONS, NOT IN CEILING.
 5) SHT A-103 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS FOR THE
 LOWER ROOFS. SHOW 1/2 AREA OF ALL VERTI-
 CAL WALLS AND SHOW ALL AREAS OF ROOFS
 THAT DRAIN ON TO LOWER ROOF FROM ABOVE.
 SECTIONS 1106, 1106.2, 1106.3, 1106.4,
 1106.5, 1106.6, 1107, 1107.1, 1107.2,
 AND 1107.3
  