Plan Review Notes For Permit 02071604 |
Permit Number |
02071604 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-12-05 00:00:00 | PROVISO:MECHANICAL PERMIT 02071605 | | | | PLAN SHEET A-101 INDICATE A 2 HR FIRE | | RATED WALL BETWEEN THE SHOWROOM AREA | | AND THE SERVICE AREA.SUPPLY DUCTS | | PENETRATING THIS WALL DO NOT REQUIRE | | FIRE DAMPERS IF INSTALLED IN ACCORDANCE | | WITH 2001 FBC(M) 607.1.3 #3 AS FOLLOWS: | | | | 1.THE DUCT SHALL NOT EXCEED SQ IN. | | (12 X 6 - OKAY) | | 2.THE DUCT SHALL BE OF .0217 IN STEEL. | | 3.THE DUCT SHALL CONTINUE WITH NO DUCT | | OPENINGS FOR NOT LESS THAN 5 FT FROM | | RATED WALL, AND | | 4.THE DUCT SHALL BE INSTALLED ABOVE | | THE CEILING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|