Plan Review Notes
Plan Review Notes For Permit 02071604
Permit Number 02071604
Review Stop M
Sequence Number 2
Notes
Date Text
2002-12-05 00:00:00PROVISO:MECHANICAL PERMIT 02071605
  
 PLAN SHEET A-101 INDICATE A 2 HR FIRE
 RATED WALL BETWEEN THE SHOWROOM AREA
 AND THE SERVICE AREA.SUPPLY DUCTS
 PENETRATING THIS WALL DO NOT REQUIRE
 FIRE DAMPERS IF INSTALLED IN ACCORDANCE
 WITH 2001 FBC(M) 607.1.3 #3 AS FOLLOWS:
  
 1.THE DUCT SHALL NOT EXCEED SQ IN.
 (12 X 6 - OKAY)
 2.THE DUCT SHALL BE OF .0217 IN STEEL.
 3.THE DUCT SHALL CONTINUE WITH NO DUCT
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 RATED WALL, AND
 4.THE DUCT SHALL BE INSTALLED ABOVE
 THE CEILING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.