2002-12-09 00:00:00 | SECOND PLAN REVIEW COMMENTS |
| |
| THE REQUESTED SURVEY AND DIMENSIONED |
| SITE PLAN HAVE NOT BEEN PROVIDED.THE |
| ARCHITECT'S RESPONSE IN THE |
| LETTER DATED 11/20/02 DOES LITTLE TO |
| ADDRESS THE CITED CODE ISSUES. |
| |
| THE AREA SHOWN AS "VW SERVICE WRITEUP" |
| IS DEEMED TO BE A PART OF THE BUILDING |
| PROPER.THE OPEN WALL AREA OF THIS |
| PORTION OF THE BUILDING IS SUBJECT TO |
| THE REQUIREMENTS OF FBC TABLE 600 AS |
| ARE THE OPEN SERVICE BAYS. |
| |
| SHEET MSP-1 DATED 6/23/02 SHOWS THE |
| WRITEUP SERVICE AREA ADJACENT TO OR |
| TOUCHING SOMETHING LABELED "VW PARTS". |
| THEREFORE THE ASSUMED PROPERTY LINE HERE |
| IS ZERO AS IT WILL BE FOR THE PROPOSED |
| ONE STORY PARKING GARAGE. |
| |
| THE VW SERVICE BAYS SHOW A SEPARATION OF |
| 28'-7".IF A PROPERTY LINE IS ASSUMED |
| IN THE CENTER, OPENING PROTECTIVES ARE |
| REQUIRED FOR THE SERVICE BAYS.ON THE |
| EAST SIDE A SIMILAR SITUATION APPEARS |
| TO EXIST FOR THE SAAB SERVICE AREA. |
| WHILE THE ARCHITECT DECLARES IN HIS |
| LETTER THAT THE SAAB SHOWROOM IS WITH |
| OUT OPENINGS, DOES THAT APPLY TO THE |
| SERVICE AREA AS WELL?FURTHER, TYPE IV |
| BUILDINGS LOCATED IN THE FIRE DISTRICT |
| ARE REQUIRED TO HAVE TWO HOUR RATED |
| EXTERIOR WALLS IN ACCORDANCE WITH FBC |
| F102.2.6 AS AMENDED BY THH CITY OF WEST |
| PALM BEACH. |
| |
| THE SUBSTITUTION OF THE FRT PLYWOOD |
| SHEATHING IS NOT THE SAME AS |
| NON-COMBUSTIBLE. SEE FBC 202 FOR THE |
| DEFINITION OF NON-COMBUSTIBLE. |
| |
| THE "CEILING" CONSTRUCTED OF PRECAST |
| HOLLOW CORE WITH ITS FIXED ACCESS |
| LADDER, ABOVE THE SUSPENDED CEILING IN |
| THE MEN'S LOCKER ROOM,APPEARED TO BE A |
| STORAGE MEZZANINE.GIVEN THAT THE |
| ARCHITECT DECLARES IN HIS LETTER THAT |
| IT IS NOT INTENDED FOR SUCH USE, PLEASE |
| INDICATE CLEARLY ON THE PLANS THAT |
| INTENT SO THAT FUTURE LIFE SAFETY AND |
| CODE ENFORCEMENT MAY BE ENSURED. |
| |
| THE INFORMATION PROVIDED FOR THE AERO |
| LITE SUNSHADE DECLARES DESIGN TO THE |
| 1997 STANDARD BUILDING CODE AND DOES |
| NOT HAVE THE ENGINEER'S ORIGINAL SEAL |
| AND SIGNATURE. |
| |
| THE ALUCOBOND PANEL INFORMATION DOES NOT |
| HAVE ANY REFERENCES TO RECOGNISED |
| TESTING LABORATORIES OR EVALUATION |
| SERVICES. |