Plan Review Notes
Plan Review Notes For Permit 02071604
Permit Number 02071604
Review Stop B
Sequence Number 2
Notes
Date Text
2002-12-09 00:00:00SECOND PLAN REVIEW COMMENTS
  
 THE REQUESTED SURVEY AND DIMENSIONED
 SITE PLAN HAVE NOT BEEN PROVIDED.THE
 ARCHITECT'S RESPONSE IN THE
 LETTER DATED 11/20/02 DOES LITTLE TO
 ADDRESS THE CITED CODE ISSUES.
  
 THE AREA SHOWN AS "VW SERVICE WRITEUP"
 IS DEEMED TO BE A PART OF THE BUILDING
 PROPER.THE OPEN WALL AREA OF THIS
 PORTION OF THE BUILDING IS SUBJECT TO
 THE REQUIREMENTS OF FBC TABLE 600 AS
 ARE THE OPEN SERVICE BAYS.
  
 SHEET MSP-1 DATED 6/23/02 SHOWS THE
 WRITEUP SERVICE AREA ADJACENT TO OR
 TOUCHING SOMETHING LABELED "VW PARTS".
 THEREFORE THE ASSUMED PROPERTY LINE HERE
 IS ZERO AS IT WILL BE FOR THE PROPOSED
 ONE STORY PARKING GARAGE.
  
 THE VW SERVICE BAYS SHOW A SEPARATION OF
 28'-7".IF A PROPERTY LINE IS ASSUMED
 IN THE CENTER, OPENING PROTECTIVES ARE
 REQUIRED FOR THE SERVICE BAYS.ON THE
 EAST SIDE A SIMILAR SITUATION APPEARS
 TO EXIST FOR THE SAAB SERVICE AREA.
 WHILE THE ARCHITECT DECLARES IN HIS
 LETTER THAT THE SAAB SHOWROOM IS WITH
 OUT OPENINGS, DOES THAT APPLY TO THE
 SERVICE AREA AS WELL?FURTHER, TYPE IV
 BUILDINGS LOCATED IN THE FIRE DISTRICT
 ARE REQUIRED TO HAVE TWO HOUR RATED
 EXTERIOR WALLS IN ACCORDANCE WITH FBC
 F102.2.6 AS AMENDED BY THH CITY OF WEST
 PALM BEACH.
  
 THE SUBSTITUTION OF THE FRT PLYWOOD
 SHEATHING IS NOT THE SAME AS
 NON-COMBUSTIBLE. SEE FBC 202 FOR THE
 DEFINITION OF NON-COMBUSTIBLE.
  
 THE "CEILING" CONSTRUCTED OF PRECAST
 HOLLOW CORE WITH ITS FIXED ACCESS
 LADDER, ABOVE THE SUSPENDED CEILING IN
 THE MEN'S LOCKER ROOM,APPEARED TO BE A
 STORAGE MEZZANINE.GIVEN THAT THE
 ARCHITECT DECLARES IN HIS LETTER THAT
 IT IS NOT INTENDED FOR SUCH USE, PLEASE
 INDICATE CLEARLY ON THE PLANS THAT
 INTENT SO THAT FUTURE LIFE SAFETY AND
 CODE ENFORCEMENT MAY BE ENSURED.
  
 THE INFORMATION PROVIDED FOR THE AERO
 LITE SUNSHADE DECLARES DESIGN TO THE
 1997 STANDARD BUILDING CODE AND DOES
 NOT HAVE THE ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE.
  
 THE ALUCOBOND PANEL INFORMATION DOES NOT
 HAVE ANY REFERENCES TO RECOGNISED
 TESTING LABORATORIES OR EVALUATION
 SERVICES.