Plan Review Notes
Plan Review Notes For Permit 02071604
Permit Number 02071604
Review Stop M
Sequence Number 1
Notes
Date Text
2002-08-23 00:00:00DENIED:
  
 1.PLAN SHEET MSP-1 INDICATES SCOPE OF
 WORK TO INCLUDE THE SERVICE AREA.
 MECHANICAL PLANS DO NOT INCLUDE ANY
 INFORMATION AS TO THE VENTILATION
 FOR THIS AREA.SHOW COMPLIANCE WITH
 2001 FBC 411.5.4.
  
 2.PLEASE PROVIDE OUTSIDE CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 AHSRAE 62-89.
  
 3.NO PROVISIONS ARE SHOWN FOR CARBON
 DIOXIDE DETECTION OR REMOVAL IN THE
 SHOWROOM AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.