Plan Review Notes For Permit 02071604 |
Permit Number |
02071604 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-23 00:00:00 | DENIED: | | | | 1.PLAN SHEET MSP-1 INDICATES SCOPE OF | | WORK TO INCLUDE THE SERVICE AREA. | | MECHANICAL PLANS DO NOT INCLUDE ANY | | INFORMATION AS TO THE VENTILATION | | FOR THIS AREA.SHOW COMPLIANCE WITH | | 2001 FBC 411.5.4. | | | | 2.PLEASE PROVIDE OUTSIDE CALCULATIONS | | AS PER 2001 FBC(M) TABLE 403.3 OR | | AHSRAE 62-89. | | | | 3.NO PROVISIONS ARE SHOWN FOR CARBON | | DIOXIDE DETECTION OR REMOVAL IN THE | | SHOWROOM AREA. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|