Plan Review Notes
Plan Review Notes For Permit 02071604
Permit Number 02071604
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PANEL "M" IS SHOWN AS 32000 BUT PANELS
 "A & B" ARE SHOWN AT 10000,PLEASE
 CLARIFY
  
 2} SHOW THE 150 AMP FEED FOR AHU-3 IN
 THE PANEL OF ORIGIN AND INCLUDE IN THE
 LOAD CALC'S FOR THAT PANEL
  
 3} PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
 4} EF #1 & 2 ARE SHOWN ON CIRCUIT A-36,
 THAT CIRCUIT IS LISTED AS A SPARE ON THE
 PANEL SCHEDULE.
  
 5} THE 8"X8"X48"WIREWAYS ON THE RISER
 DIAGRAM ARE LISTED AS 6"X6"X48" IN THE
 NOTES.WHICH IS INTENDED TO BE USED?
  
 6} WHAT UNIT LOAD PER SQ.FT.WAS USED IN
 ARRIVING AT THE GENERAL LIGHTING LOAD
 FOR THE CALCULATIONS?
  
 7} PANEL "M" IS RATED AT 400 AMPS BUT
 THE CONNECTED LOADS INDICATED ARE OVER
 400 AMPS,PLEASE MAKE NECESSARY
 CORRECTIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392