Date |
Text |
2002-08-12 00:00:00 | PLEASE PROVIDE A PROPERTY SURVEY.ON |
| THE SITE PLAN SHOW THE DIMENSIONS |
| BETWEEN BUILDINGS, CONSTRUCTION TYPE OF |
| EXISTING BUILDINGS AND THE PERCENTAGE |
| OF OPENINGS IN THE EXTERIOR WALLS SO |
| THAT COMPLIANCE WITH FBC TABLE 600 MAY |
| BE DETERMINED.SEE ALSO, THE MINIMUM |
| PLAN REVIEW CRITERIA CONTAINED IN FBC |
| 104.3.1.1 AND 104.2.4. |
| |
| DETAIL 1 ON SHEET A-108, AND ELSEWHERE, |
| INDICATE THE USE OF PLYWOOD IN THE |
| EXTERIOR WALL ASSEMBLIES WHICH IS TYPE |
| VI CONSTRUCTION.THIS CONSTRUCTION TYPE |
| IS NOT PERMITTED IN THE DESIGNATED FIRE |
| DISTRICT.SEE FBC APPENDIX A FBC 102.1 |
| AS AMENDED BY THE CITY, AND REVISE AS |
| NECESSARY. |
| |
| THE FRITTED GLASS IN THE ENTRANCE CANOPY |
| MUST COMPLY WITH FBC 2405.3.2.1. |
| |
| PLEASE PROVIDE INFORMATION ON THE "ALUCO |
| BOND PANELS" AND THE "AERO LITE SUN |
| SHADE".SEE FBC 104.2. |
| |
| SHOW THE DESIGN LOAD FOR THE MEZZANINE |
| ABOVE THE MEN'S LOCKER ROOM AND EGRESS |
| REQUIREMENTS COMPLYING WITH FBC |
| 1005.7.3. |
| |
| SHOW THE FIRE RATED SEPARATION BETWEEN |
| THE SERVICE AREA AND THE SHOWROOM, |
| GROUPS S AND B, IN ACCORDANCE WITH FBC |
| 411.5. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO THE |
| COUNTY, THE PERMIT PLANS STAMPED BY |
| THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |