Plan Review Notes
Plan Review Notes For Permit 02071604
Permit Number 02071604
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-12 00:00:00PLEASE PROVIDE A PROPERTY SURVEY.ON
 THE SITE PLAN SHOW THE DIMENSIONS
 BETWEEN BUILDINGS, CONSTRUCTION TYPE OF
 EXISTING BUILDINGS AND THE PERCENTAGE
 OF OPENINGS IN THE EXTERIOR WALLS SO
 THAT COMPLIANCE WITH FBC TABLE 600 MAY
 BE DETERMINED.SEE ALSO, THE MINIMUM
 PLAN REVIEW CRITERIA CONTAINED IN FBC
 104.3.1.1 AND 104.2.4.
  
 DETAIL 1 ON SHEET A-108, AND ELSEWHERE,
 INDICATE THE USE OF PLYWOOD IN THE
 EXTERIOR WALL ASSEMBLIES WHICH IS TYPE
 VI CONSTRUCTION.THIS CONSTRUCTION TYPE
 IS NOT PERMITTED IN THE DESIGNATED FIRE
 DISTRICT.SEE FBC APPENDIX A FBC 102.1
 AS AMENDED BY THE CITY, AND REVISE AS
 NECESSARY.
  
 THE FRITTED GLASS IN THE ENTRANCE CANOPY
 MUST COMPLY WITH FBC 2405.3.2.1.
  
 PLEASE PROVIDE INFORMATION ON THE "ALUCO
 BOND PANELS" AND THE "AERO LITE SUN
 SHADE".SEE FBC 104.2.
  
 SHOW THE DESIGN LOAD FOR THE MEZZANINE
 ABOVE THE MEN'S LOCKER ROOM AND EGRESS
 REQUIREMENTS COMPLYING WITH FBC
 1005.7.3.
  
 SHOW THE FIRE RATED SEPARATION BETWEEN
 THE SERVICE AREA AND THE SHOWROOM,
 GROUPS S AND B, IN ACCORDANCE WITH FBC
 411.5.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.