Date |
Text |
2002-09-30 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | 1} THE SCOPE OF WORK ON THE ORIGINAL | | APPLICATION WAS FOR REPLACING KITCHEN | | CABINETS,AND THE ELECTRICAL PERMIT | | APPLICATION STATED "PER PLANS".THERE | | WERE NO PLANS SUBMITTED FOR REVIEW | | UNTILL THIS SET,AND THE WORK WAS | | OBVIOUSLY MORE EXTENSIVE THAN THE | | KITCHEN.PLEASE PROVIDE A NEW VALUATION | | REFLECTING THE SCOPE OF WORK BEING DONE | | PER 104.6.5 CWPB AMMENDMENTS.(ATTACHED). | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE,AND | | INDICATE THE SIZE OF THE SERVICE. | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG.PUT SAME ON PANEL | | SCHEDULE. | | | | 4} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | 5} PLEASE INDICATE THE REQUIRED KITCHEN | | CICUITS ON PANEL SCHEDULE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|