Date Text
2002-09-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} THE SCOPE OF WORK ON THE ORIGINAL
 APPLICATION WAS FOR REPLACING KITCHEN
 CABINETS,AND THE ELECTRICAL PERMIT
 APPLICATION STATED "PER PLANS".THERE
 WERE NO PLANS SUBMITTED FOR REVIEW
 UNTILL THIS SET,AND THE WORK WAS
 OBVIOUSLY MORE EXTENSIVE THAN THE
 KITCHEN.PLEASE PROVIDE A NEW VALUATION
 REFLECTING THE SCOPE OF WORK BEING DONE
 PER 104.6.5 CWPB AMMENDMENTS.(ATTACHED).
  
 2} PLEASE PROVIDE A PANEL SCHEDULE,AND
 INDICATE THE SIZE OF THE SERVICE.
  
 3} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.PUT SAME ON PANEL
 SCHEDULE.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE INDICATE THE REQUIRED KITCHEN
 CICUITS ON PANEL SCHEDULE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392