Plan Review Notes
Plan Review Notes For Permit 02071381
Permit Number 02071381
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-02 00:00:001) PLEASE CLEARLY ILLUSTRATE ALL
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES.
  
 2) ALL ELECTRICAL, MECHANICAL, AND
 SERVICE ROOMS ARE REQUIRED TO BE AT
 LEAST ONE HOUR FIRE RATED WITH RATED
 OPENING PROTECTIVE DEVICES IF FIRE
 SPRINKLERS ARE NOT PRESENT.
  
 3) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED WITHIN TENANT SPACES.
  
 4) SECURITY DEVICES INSTALLED ON INGRESS
 AND EGRESS DOORS SHALL NOT INTERFERE
 WITH EXITING.
  
 5) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED FOR WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497