Plan Review Notes
Plan Review Notes For Permit 02071381
Permit Number 02071381
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-25 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE CIRCUITING NEEDS TO
 BE SHOWN ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE CLARIFY NEW OR/ EXISTING
 EM LTS? EXIT LTS ARE SHOWN AS NEW.
  
 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 RECEPTS PER 210-62
  
 4)NOTE: PLEASE CLARIFY SIGN CIRCUIT
 REQ`D PER 600-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372