Notes |
Date |
Text |
2002-07-25 00:00:00 | ***************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE CIRCUITING NEEDS TO | | BE SHOWN ON PLANS AND CORRELATE WITH A | | SUBMITTED PANEL SCHEDULE. | | | | 2)NOTE: PLEASE CLARIFY NEW OR/ EXISTING | | EM LTS? EXIT LTS ARE SHOWN AS NEW. | | | | 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | RECEPTS PER 210-62 | | | | 4)NOTE: PLEASE CLARIFY SIGN CIRCUIT | | REQ`D PER 600-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|