2002-07-19 00:00:00PLUMBING PLAN REVIEW, DENIED
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 3. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 LEGIBLE CUT SHEETS TO SHOW BTU'S.
 5.NFPA-58,SEC 3.2.2.6(H) TO PREVENT FLOT
 ATION, UNDER GROUND TANKS SHALL BE
 SECURLEY ANCHORED.
 6 NFPA-96 SEC 5.5.4 EMERGENCY HOOD SOV
 TO BE BELOW CEILING, MANUAL SOV TO BE UP
 STREAM, UNION TO BE DOWN STREAM OF THE
 MANUAL SOV.
 8. SGC-97 SEC 104.2.3 PLANS TO BE SIGNED
 AND SEALED BY ENGINEER OF RECORD
 END OF COMMENTSPAUL SCHMITZ