 BUILDING PLAN REVIEW
 PERMIT: 02071111
 ADD: 2645 SANDY CAY
 CONT: TAZ CONSTRUCTION
 TEL: (954)340-1744
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ******PROVISO*****
  
 PROVIDE MISSING PRODUCT REPORTS BEFORE
 FRAMING INSPECTION:
 A) SWING DOORS
 B) GLASS BLOCK
 C) ROOFING ASSEMBLIES
 CONNECTION DETAIL 15 OF SHEET A5, ON A
 SINGLE MEMBER TRUSS THE VALUES GIVEN
 FOR THE TA-14R OF 1520 @ EACH STRAP
 EQUAL 3040 , A DERATING OF 20% IS RECOME
 NDED BY USP OR A VALUE OF 2432 PLUS 785
 FOR THE MSH218 OR A TOTAL ALLOWABLE LOAD
 OF 3217, THIS IS LIGHT VS THE 3833
 MAXIMUM UPLIFT.
  
 THE USE OF A 2 MEMBER MSH418 FACE MOUNT
 WITH (2) TA-14R WITH REDUCTION ADEQUATE-
 LY MEETS THE REQUIRED RESISTANCE FOR
 UPLIFT.
 BUILDING PLAN REVIEW
 JIM WITMER