Plan Review Notes For Permit 02071111 |
Permit Number |
02071111 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-15 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 02071111 | | ADD: 2645 SANDY CAY | | CONT: TAZ CONSTRUCTION | | TEL: (954)340-1744 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | ******PROVISO***** | | | | PROVIDE MISSING PRODUCT REPORTS BEFORE | | FRAMING INSPECTION: | | A) SWING DOORS | | B) GLASS BLOCK | | C) ROOFING ASSEMBLIES | | CONNECTION DETAIL 15 OF SHEET A5, ON A | | SINGLE MEMBER TRUSS THE VALUES GIVEN | | FOR THE TA-14R OF 1520 @ EACH STRAP | | EQUAL 3040 , A DERATING OF 20% IS RECOME | | NDED BY USP OR A VALUE OF 2432 PLUS 785 | | FOR THE MSH218 OR A TOTAL ALLOWABLE LOAD | | OF 3217, THIS IS LIGHT VS THE 3833 | | MAXIMUM UPLIFT. | | | | THE USE OF A 2 MEMBER MSH418 FACE MOUNT | | WITH (2) TA-14R WITH REDUCTION ADEQUATE- | | LY MEETS THE REQUIRED RESISTANCE FOR | | UPLIFT. | | BUILDING PLAN REVIEW | | JIM WITMER |
|