2002-08-08 00:00:00 | PROVISO:MECHANICAL PERMIT 02070906 | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | AS PER 2001 FBC(M) 1108.1, REFRIGERANT | | LINES SHALL BE TESTED.TEST SHALL BE | | PERFORMED WITH AN INERT DRIED GAS | | INCLUDING, BUT NOT LIMITED TO, NITROGEN | | & CARBON DIOXIDE 2001 FBC(M) 1108.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|