Plan Review Notes For Permit 02070823
Permit Number 02070823
Review Stop M
Sequence Number 1
Notes
Date Text
2002-08-08 00:00:00PROVISO:MECHANICAL PERMIT 02070906
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.