2002-08-08 00:00:00PROVISO:MECHANICAL PERMIT 02070898
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.2001 FBC(M) 303.4
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  