Plan Review Notes For Permit 02070816 |
Permit Number |
02070816 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-07 00:00:00 | PROVISO:MECHANICAL PERMIT 02070890 | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | REFRIGERANT LINES SHALL BE TESTED AS PER | | 2001 FBC(M) 1108.1.TEST SHALL BE PER- | | FORMED WITH AN INERT DRIED GAS (SUCH AS | | NITROGEN) 2001 FBC(M) 1108.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|