Plan Review Notes
Plan Review Notes For Permit 02070761
Permit Number 02070761
Review Stop P
Sequence Number 3
Notes
Date Text
2002-12-05 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) FROM PREVIOUS REVIEW DATED 7-15-02
 BY PAUL SCHMITZ. SEPARATE PERMITS REQUI-
 RED FOR EACH PUMP STATION. SEPARATE
 ADDRESS FOR EACH PUMP STATION.
  
 SECTION 104.2 DRAWINGS & SPECIFICATIONS
 AS REQUIRED 104.3.1.1 TWO OR MORE COPIES
 OF SPECIFICATIONS, AND OF DRAWINGS DRAWN
 TO SCALE WITH SUFFICENT CLARITY AND DE-
 TAIL TO INDICATE THE NATURE AND CHARACT-
 ER OF WORK, INCLUDING ELECTRICAL. PLANS
 TO BE SIGNED AND SEALED BY A FLORIDA
 REGISTERED ENGINEER.
  
 EACH PERMIT SHALL HAVE IT'S OWN SET OF
 PLANS. PLEASE APPLY FOR NEW PERMIT WITH
 NEW PLANS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377