2002-07-23 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT SMALL APPLIANCE
 CIRCUITS NEED TO BE INCLUDED IN LOAD
 CALCULATIONS PER 210-52B AND 210-11-C-1
  
 2)NOTE: PLEASE NOTE SD`S ARE NOT PERMITT
 ED IN BATHROOMS PER NFPA-72 2-5.2.1.6
  
 3)NOTE: PLEASE NOTE THAT NO EQUIPMENT
 GROUDING COUNDUCTOR BETWEEN METER
 AND MAIN DISC. THIS IS PARALLELING THE
 NEUTRAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  