Date Text
2002-08-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070435
 ADD: 10510 TERRA LAGO DRIVE
 CONT: CLASSIC DESIGNER HOMES
 TEL: (954)345-2727
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) BUTT GLAZING: SITE SPECIFIC ENGINEER-
 ING, TO BE SITE SPECIFIC, ARCHITECT OR
 DESIGNER OF RECORD TO SEAL THE RIGHT
 SIDE OF FORM OR ATTACH A SEALED AFFIDA-
 VIT ATTESTING THIS PRODUCT SHALL MEET
 THE DESIGN CRITERIA OF THIS OPENING.
 THE SECOND ISSUE IS THE FORM INDI-
 CATES THE USE OF 1/4" GLASS WHEREAS THE
 ENGINEERING SHEET INDICATES 1/2"?
 GENERAL NOTES FOR BUTT GLAZING(6)
 SILICONE SEALENT PER WINDOW MANUFACT-
 URERS RECOMMENDATION. WHAT IS IT?
 SHEET A-4 REAR ELEVATION FOR THE BUTT
 GLASS INDICATES (12) 142"X90". SHEET A7,
 A13 INDICATES A "B-3" NO HEIGTH? PLEASE
 PROVIDE A CUT SECTION THROUGH OR ADDI-
 TIOAL INFORMATION.
  
 2) SHEET A-5 TABLE 600, WALL AREA IS
 FIGURED FROM FLOOR TO CEILING PER FLOOR,
 IN THIS CASE THE FLOOR TRUSSES ARE TO BE
 DEDUCTED OR 69 SQ FT REDUCING THE 20%
 ALLOWABLE AREA FROM 89.72 SQ FT TO
 75.92 SQ FT. THIS IS WITHOUT ADDING THE
 GLASS BLOCK OPENINGS, ALTHOUGH THE GLASS
 WILL NOT REQUIRE A 1 HR RATING, WE WILL
 NEED ADDITIONAL RATING (45MIN) TO NOT
 FIGURE IT AS PART OF THE ALLOWABLE
 WALL OPENINGS.
  
 3) SHEET A2/A7 INDICATES L-4, L-6 TO SIT
 ON THE SAME 8"X8" BLOCK COLUMN. 2101.3.1
 LINTEL, THE MINIMUM END BEARING SHALL
 BE 4", INDICATE HOW THIS WILL BE
 ACCOMPLISHED?
  
 4) SHEET A-7 / SEC 30/14 SEE 1511.6.3
 FLASHINGS: PROPER FLASHING SHALL BE IN-
 STALLED IN SUCH A MANNER AS TO PREVENT
 MOISTURE ENTERING THE WALL, INDICATE HOW
 WALL WILL BE FLASHED, SURFACE OF DECK
 AND HOW BLOCK WITH STEEL REBAR SHALL
 BE FLASHED?
  
 5) SHEET A-14 DETAIL 17 INDICATES A
 HOLD DOWN DEVICE SHA6T WITH A DESIGN
 LOAD OF 9,830 LBS.USP INDICATES AN
 ALLOWABLE UPLIFT OF 7550 LBS. NOTE 1
 NO ADDITIONAL ALLOWABLE LOADING MAY BE
 TAKEN!
  
 6) THIS SAME AREA, SHEET A-10 DETAIL
 1-A8 INDICATES A WALL SECTION TO THE
 RIGHT OF THE GIRDER WHERE DOES THIS GO?
  
 7) SHEET A-4 DETAIL 3, WALL MOUNT GUARD
 RAIL VS ELEVATIONS DO NOT MATCH, ELEVA-
 TION INDICATES 42" HEIGHT, DETAIL 48"
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 SAME DETAIL CORRECT STATEMENT "SOUTHERN
 BUILDING CODE".
  
 8) 1007.3.1 TREADS / RISERS: (1)
 EVERY TREAD LESS THAN 10" SHALL HAVE A
 NOSING, OR EFFECTIVE PROJECTION OF AP-
 PROXIMATELY 1 INCH OVER THE LEVEL IMMED-
 IATELY BELOW THAT TREAD.
  
 9)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 10)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026