Plan Review Notes
Plan Review Notes For Permit 02070435
Permit Number 02070435
Review Stop M
Sequence Number 1
Notes
Date Text
2002-07-26 00:00:00PROVISO:MECHANICAL PERMIT 02070439
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 AHU IN GARAGE -
 APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.2001 FBC(M) 303.4
  
 SHOULD A GAS DRYER BE INSTALLED -
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.
  