2002-07-30 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING:
  
 1} THE "POWDER ROOM" ON SHEET A-11 IS
 MISSING A GFI PER 210-52(D).
  
 2} THERE ARE TWO PANELS SHOWN IN THE
 GARAGE ON SHEET A-11 AND ONLY ONE ON
 THE RISER DIAGRAM ON SHEET A-13.
  
 3} THE 4.8VA AHU HEAT STRIP LISTED ON
 THE PANEL SCHEDULE DOES NOT COMPLY WITH
 424-3(B)@ 125%.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392