2002-08-13 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02070387 |
| 02070389 |
| ADD: 2448 SANDY CAY MODEL C |
| 2452 SANDY CAY MODEL B |
| CONT: TAZ |
| TEL: (954)340-1744 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) FRONT DOOR W/ TRANSOM |
| B) WINDOWS |
| C)MULLIONS |
| D) SLIDING GLASS DOOR |
| E) ROOFING ASSEMBLIES |
| |
| 3)SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL |
| OF RECORD. |
| |
| 4)1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 5)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 6)1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 7) FL BLD CODE 2405.2 HAZARDOUS LOCATION |
| PROVIDE SAFETY GLASS FOR THIS LOCATION: |
| LOT #3 MASTER BATH PROVIDE MAN SPEC FOR |
| GLASS BLOCK WALL THICKNESS, |
| SEE 2405.2.2(5) MINIMUM WALL THICKNESS |
| REQUIREMENT FOR HAZARDOUS AREAS. |
| |
| 8) 1707.3.1 JOIST HANGERS, FRAMING |
| ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| LABELED AND LISTED FOR THEIR LOAD CARRY- |
| ING CAPACITY.SHEET 7 ANCHOR LEGEND |
| ANCHOR (2) USING TWO HETAL 20'S AND |
| ULTIMATE LOAD OF 3700 LBS. SIMPSON |
| TECHNICAL SUPPORT DERATES THIS PRODUCT |
| USED ON A 2 MEMBER GIRDER SPACED 3" |
| APART TO AN ALLOWABLE 2500 LBS MAX!!!!! |
| FOR MORE LOADING PROVIDE AN ENGINEERS |
| SIGNED/ SEALED LETTER.SEE INSTRUCTIONS |
| FOR DESIGNER NOTE (I) FOR TESTING DATA. |
| |
| 9 BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |