Plan Review Notes For Permit 02070247 |
Permit Number |
02070247 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-26 00:00:00 | DENIED:MECHANICAL PERMIT 02070349 | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | AIR (JUMPER). | | | | PLEASE NOTE ENERGY CALCS INDICATE A 4 | | TON SYSTEM & PLANS INDICATE ONLY A 3.5 | | TON.THE CONDITION SPACE IS 1975 SQ FT. | | PLEASE CORRELATE EQUIPMENT SPECIFIED, | | THE MANUAL J & ENERGY CALCS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|