2002-07-26 00:00:00DENIED:MECHANICAL PERMIT 02070349
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 PLEASE NOTE ENERGY CALCS INDICATE A 4
 TON SYSTEM & PLANS INDICATE ONLY A 3.5
 TON.THE CONDITION SPACE IS 1975 SQ FT.
 PLEASE CORRELATE EQUIPMENT SPECIFIED,
 THE MANUAL J & ENERGY CALCS.
  