| BUILDING PLAN REVIEW |
| PERMIT: 02070213 |
| ADD: 6406 CROWN ISLAND COVE |
| CONT: M/I HOMES |
| TEL: (561)471-3440 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING OR ADDITION |
| AL INFORMATION REQUIRED: |
| A) WINDOWS: BUTT GLAZING: 2406.2 |
| SPECIAL CASES, WHERE OTHER THAN FIRM SUP |
| PORT ON ALL SIDES IS PROVIDED, (THREE |
| SIDES, TWO SIDES, CANTILEVERED, OR HIGH- |
| LY FLEXIBLEFOR EXAMPLE) DETAILED SHOP |
| DRAWINGS SPECIFICATIONS AND RATIONAL |
| ANALYSIS AND OR TEST DATA ASSURING THE |
| SAFE PERFORMANCE FOR THE SPECIFIC |
| INSTALLATION SHALL BE PREPARED BY |
| ENGINEERS EXPERIENCED IN THIS WORK AND |
| SHALL BE SUBMITTED FOR AND RECEIVE, IF |
| WARRENTED FORMAL APPROVAL BY THE BUILD- |
| ING OFFICIAL.PROVIDE DATA. |
| B)OVERHEAD GARAGE DOOR, SPECIFY OR HIGH |
| LIGHT WHICH MODEL SHALL BE USED. |
| C) STORM SHUTTERS, ELEVATIONS MISSING |
| PRESSURES POS/ NEG ON ARCHETECTURAL |
| SHEETS. |
| SITE SPECIFIC: NOT FILLED OUT BY |
| THE ARCHETECT, MISSING ADDRESS. |
| ENGINEERING NOT SIGNED BY ENGINEER |
| OF RECORD. |
| AS PER CITY IMPLEMENTATION STANDARD |
| FOR HURRICANE MISSLE IMPACT PROTECTION. |
| SECTIONS TO BE USED NOT HIGHLIGHTED. |
| NO KEY PLAN IDENTIFYING OPENINGS FOR |
| IDENTIFYING WINDOWS VS SHUTTERS. |
| SCHEDULE DOESN'T INDICATE FASTENER |
| TO BE USED, SPACING MAY BE OFF. |
| SCHEDULE DOESN'T INDICATE SHUTTERS |
| TO BE INSTALLED HORIZONTALLY OR VERTICAL |
| D) SHEET 9 OF 9: -66.1 PRESSURE ???? |
| THE PRODUCT APPROVALS DO NOT COME CLOSE |
| TO THIS PRESSURE. |
| |
| 3) FAMILY ROOM: SLIDING GLASS DOOR OPEN- |
| ING, WILL THE TRACK FOR (4) DOORS AND |
| SCREEN FIT UNDER THE BEAM? |
| |
| 4) FAMILY ROOM: (4 1/2") WALL MADE OF |
| WHAT MATERIALS? ANCHORED HOW? |
| |
| 5) FAMILY ROOM: THE WALL ABOVE THE |
| 8"X23"INDICATES THAT IT HAS SHEER WALL |
| SECTIONS, FASTENED HOW? BUILT OUT OF |
| WHAT MATERIALS? THICKER THAN THE REST OF |
| THE WALLS? |
| |
| 6) THE LOAD OF THE SECOND STORY WALL IS |
| TRANSFERED ONTO A 8"X23" BEAM THE ONE |
| END IS SUPPORTED BY 45 DEGREE COLUMN W/ |
| 2/#5'S??? |
| |
| 7) THE SAME WALL SECTION, BUTT GLAZING, |
| NO DETAILS AS TO HOW IT IS ATTCHED SIDES |
| OR TOP? CANTILEVERED BEAM ABOVE. |
| |
| 8) MISSING ROOF FRAMING MEMBERS AT THE |
| BUTT GLASS DETAIL. |
| |
| 9) CANTILEVERED TRUSSES, EXTERIOR OF THE |
| FAMILY ROOM, NO DETAILS? |
| |
| 10) FLOOR TRUSS OR GIRDER (LAST TRUSS) |
| ACHIEVE SUPPORT? BETWEEN FAMILY ROOM AND |
| THE KITCHEN? |
| |
| 11) HOW DOES SHEETS A&B RELATE TO THE |
| REMAINDER OF THE JOB? THERE ARE DETAILS |
| WITH NO INFORMATION? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |