Plan Review Notes
Plan Review Notes For Permit 02070213
Permit Number 02070213
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070213
 ADD: 6406 CROWN ISLAND COVE
 CONT: M/I HOMES
 TEL: (561)471-3440
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING OR ADDITION
 AL INFORMATION REQUIRED:
 A) WINDOWS: BUTT GLAZING: 2406.2
 SPECIAL CASES, WHERE OTHER THAN FIRM SUP
 PORT ON ALL SIDES IS PROVIDED, (THREE
 SIDES, TWO SIDES, CANTILEVERED, OR HIGH-
 LY FLEXIBLEFOR EXAMPLE) DETAILED SHOP
 DRAWINGS SPECIFICATIONS AND RATIONAL
 ANALYSIS AND OR TEST DATA ASSURING THE
 SAFE PERFORMANCE FOR THE SPECIFIC
 INSTALLATION SHALL BE PREPARED BY
 ENGINEERS EXPERIENCED IN THIS WORK AND
 SHALL BE SUBMITTED FOR AND RECEIVE, IF
 WARRENTED FORMAL APPROVAL BY THE BUILD-
 ING OFFICIAL.PROVIDE DATA.
 B)OVERHEAD GARAGE DOOR, SPECIFY OR HIGH
 LIGHT WHICH MODEL SHALL BE USED.
 C) STORM SHUTTERS, ELEVATIONS MISSING
 PRESSURES POS/ NEG ON ARCHETECTURAL
 SHEETS.
 SITE SPECIFIC: NOT FILLED OUT BY
 THE ARCHETECT, MISSING ADDRESS.
 ENGINEERING NOT SIGNED BY ENGINEER
 OF RECORD.
 AS PER CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSLE IMPACT PROTECTION.
 SECTIONS TO BE USED NOT HIGHLIGHTED.
 NO KEY PLAN IDENTIFYING OPENINGS FOR
 IDENTIFYING WINDOWS VS SHUTTERS.
 SCHEDULE DOESN'T INDICATE FASTENER
 TO BE USED, SPACING MAY BE OFF.
 SCHEDULE DOESN'T INDICATE SHUTTERS
 TO BE INSTALLED HORIZONTALLY OR VERTICAL
 D) SHEET 9 OF 9: -66.1 PRESSURE ????
 THE PRODUCT APPROVALS DO NOT COME CLOSE
 TO THIS PRESSURE.
  
 3) FAMILY ROOM: SLIDING GLASS DOOR OPEN-
 ING, WILL THE TRACK FOR (4) DOORS AND
 SCREEN FIT UNDER THE BEAM?
  
 4) FAMILY ROOM: (4 1/2") WALL MADE OF
 WHAT MATERIALS? ANCHORED HOW?
  
 5) FAMILY ROOM: THE WALL ABOVE THE
 8"X23"INDICATES THAT IT HAS SHEER WALL
 SECTIONS, FASTENED HOW? BUILT OUT OF
 WHAT MATERIALS? THICKER THAN THE REST OF
 THE WALLS?
  
 6) THE LOAD OF THE SECOND STORY WALL IS
 TRANSFERED ONTO A 8"X23" BEAM THE ONE
 END IS SUPPORTED BY 45 DEGREE COLUMN W/
 2/#5'S???
  
 7) THE SAME WALL SECTION, BUTT GLAZING,
 NO DETAILS AS TO HOW IT IS ATTCHED SIDES
 OR TOP? CANTILEVERED BEAM ABOVE.
  
 8) MISSING ROOF FRAMING MEMBERS AT THE
 BUTT GLASS DETAIL.
  
 9) CANTILEVERED TRUSSES, EXTERIOR OF THE
 FAMILY ROOM, NO DETAILS?
  
 10) FLOOR TRUSS OR GIRDER (LAST TRUSS)
 ACHIEVE SUPPORT? BETWEEN FAMILY ROOM AND
 THE KITCHEN?
  
 11) HOW DOES SHEETS A&B RELATE TO THE
 REMAINDER OF THE JOB? THERE ARE DETAILS
 WITH NO INFORMATION?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026