Plan Review Notes For Permit 02070045 |
Permit Number |
02070045 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-12-19 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). - BTU LOAD FOR WATER HEATER ON | | MANUF. INFO SHOWS 60,000 BTU, BUT REVIS- | | ION SHOWS 40,OOO BTU. PLEASE CLAIRFY. | | 3. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). - LONGEST RUN | | INDICATED ON REVISION SAYS 47 FEET, BUT | | IT SEEMS THAT THE UNDERGROUND PIPING IS | | NOT ADDED TO TOTAL. PLEASE CLAIRFY. | | 4) A SHUT OFF VALVE UPSTREAM OF REGULAT- | | OR WITH A UNION IN BETWEEN IS REQUIRED. | | 5) PLEASE SUBMIT A MANUF. CUT SHEET FOR | | REGULATORS BEING USED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|