2002-12-19 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - BTU LOAD FOR WATER HEATER ON
 MANUF. INFO SHOWS 60,000 BTU, BUT REVIS-
 ION SHOWS 40,OOO BTU. PLEASE CLAIRFY.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - LONGEST RUN
 INDICATED ON REVISION SAYS 47 FEET, BUT
 IT SEEMS THAT THE UNDERGROUND PIPING IS
 NOT ADDED TO TOTAL. PLEASE CLAIRFY.
 4) A SHUT OFF VALVE UPSTREAM OF REGULAT-
 OR WITH A UNION IN BETWEEN IS REQUIRED.
 5) PLEASE SUBMIT A MANUF. CUT SHEET FOR
 REGULATORS BEING USED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377