Plan Review Notes
Plan Review Notes For Permit 02070032
Permit Number 02070032
Review Stop R
Sequence Number 2
Notes
Date Text
2002-09-04 00:00:00SECOND CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ENTRY DOORS SIZE TO PROVIDE THE
 32" MIN. CLEAR OPENING REQUIRED BY
 TABLE 1004 FBC 2001.
 3-WINDOW @ ENTRY PORCH EXCEEDS MAX. % OF
 OPENINGS ALLOWED BY TABLE 600 FBC 2001
 **NOTE: NOTE #37 ON FLOOR PLAN WAS NOT
 CHANGED.
 4-SPECIFY FIREBLOCKING MATERAILS AND
 LOCATION AT STAIRS. INCLUDING AT TOP
 OF STAIRS. SEC. 2305.1.4 FBC 2001.
 **NOTE: ALSO, PROVIDE GENERAL SPECS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES AS REQ'D BY SEC. 2305.1.4 FBC.
 5-PROVIDE DRAFSTOPPING AT AREAS NOT TO
 EXCEED 500 S.F. SEC. 2305.2.2 FBC 2001
 6-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 7-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A SE-
 PARATE PERMIT AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSILE IMPACT PROTECTION.
 **NOTE: NEED SIGNED AND SEALED DWGS AS
 REQUIRED BY THE ENGINEER. ALSO NEED
 ADDITIONAL ENGINEERING FOR SPECIFIC
 MOUNTING INSTALLATION. SEE LIMITATIONS
 ON PRODUCT APPROVAL SHEET 4 OF 4.
 8-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAIL TO BE BET. 34" AND 38"
 MAX. SEE SEC. 1007.5.1 FBC 2001.
 9-SECOND FLOOR FRAMING PLAN: PROVIDE
 DETAIL SHOW'G HOW USP HL210 PURLING
 HANGER APPLIED TO HOLD GIRDER TRUSSES.
 **IMPORTANT. SEE USP CATALOGUE FOR USE
 AND CORRECT LOADS.
 10-SECTION 4/S3 IS CALLED 5/S3 ON ROOF
 PLAN. REVISE AS REQUIRED.
 11-REVISE TRUSS CONNECTOR SCHEDULE. SEE
 USP CATALOGUE.
 **NOTE A) PROVIDE ENGINEERING CALCS FOR
 LOADS DIFFERENT THAN THOSE ON USP.
 **NOTE B) TAKE INTO CONSIDERATION THAT
 10D NAILS NEED 1 3/4" MIN. PENETRATION
 TO GET FULL VALUE.
 **NOTE C) MAKE SURE THAT IF CHANGING THE
 NAIL TYPE,THEN VALUES SHALL BE CHANGED
 ACCORDINGLY.
 12-SOME CONNECTORS ARE MISSING ON ROOF
 FRAMING PLAN. EG: SPECIFY CONNECTOR
 FOR A CALCULATED UPLIFT OF 2537#.
 13-CONNECTOR TC-5 DOESN'T RESIST THE
 LOADS CALCULATED ON ROOF FRAMING PLAN
 FOR GIRDER TRUSS AT RIGHT HAND SIDE.
 14-ROOF SHEATHING & NAILING NOTE ON DWG
 S3, SECTION 4/S3 & DIAPHRAGM SCHEDULE
 HAVE DIFFERENT SPECS. REVISE AS REQ'D.
 **NOTE: KEEP IN MIND THAT FOR MEAN ROOF
 HEIGHT BET. 25' & 35' NEED TO USE 8D
 RING SHANK MIN. AS REQUIRED BY TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 15-SHOW NAILING ZONES IN ROOF FRAMING
 PLAN. SEE TABLE 2306.1 CITY AMENDMENTS
 16-DESIGN PRESSURES FOR ENTRY DOORS ARE
 SHOWN DIFFERENT ON THE FLOOR PLAN AND
 THE EXTERIOR ELEVATION. REVISE S REQ'D
 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS & REVISE
 DETAIL AS REQUIRED.
 **NOTE A)KEEP IN MIND THAT STRUCTURE IS
 NOT POURED CONCRETE BUT CONCRETE BLOCK
 **NOTE B)DON'T FORGET TO SPECIFY WASHER
 SIZE. SEC. 104.2.1.2 CITY AMENDMENTS.
 18-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ATTACHMENT OF DOUBLE 2X BUCK FOR ENTRY
 DOORS WHEN MASONRY OPENING IS REVISED
 TO RECEIVE (2)3'-0" WIDE DOORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 19-SHEET A2: UPDATE NOTE #6. REFERENCE
 FLORIDA PLUMBING CODE 2001, NOT SBC/94