Plan Review Notes
Plan Review Notes For Permit 02070032
Permit Number 02070032
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-22 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ENTRY DOORS SIZE TO PROVIDE THE
 32" MIN. CLEAR OPENING REQUIRED BY
 TABLE 1004 FBC 2001.
 3-WINDOW @ ENTRY PORCH EXCEEDS MAX. %
 OF OPENINGS ALLOWED BY TABLE 600 FBC.
 4-SPECIFY FIREBLOCKING MATERIALS AND
 LOCATION AT STAIRS. INCLUDING AT TOP
 OF STAIRS. SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECS FOR REQ'D
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEE SEC. 2305.1.4 FBC 2001.
 5-SPECIFY DRAFTSTOPPING LOCATIONS AND
 MATERIAL @ 2ND FL. FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 **NOTE: FIRESTOPPING TO BE PLACE AT
 AREAS NOT TO EXCEED 500 S.F.
 6-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 7-PROVIDE SOIL TEST REPORT.
 8-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC
 9-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM PANELS OR APPLY FOR SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 10-PROVIDE PRODUCT APPROVAL FOR DOORS,
 WINDOWS AND WINDOW MULLIONS ASSEMBLIES
 11-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAILS TO BE BET. 34" & 38"
 MAX. SEE SEC. 1007.5.1 FBC 2001.
 12-SECOND FLOOR FRAMING PLAN:
 PROVIDE DETAIL SHOWING HOW USP HANGER
 HL210 IS APPLIED ON GIRDER TRUSSES
 RESTING ON THE MASONRY WALL BY THE 2
 SIDES OF STAIRWAY. SEE USP CATALOGUE
 FOR SIZE OF HANGER AND LOAD CAPACITY.
 13-SECTION 4 OF S3 IS CALLED 5/S3 ON
 ROOF PLAN. REVISE AS REQUIRED.
 14-NOTE ON BUCKET DETAILS SHEET S2 CALLS
 FOR 1/4" WELDING. ALL BUCKET DETAILS
 CALL FOR 3/16". REVISE AS REQUIRED.
 15-REVISE TRUSS CONNECTOR SCHEDULE:
 SEE USP CATALOGUE FOR CALCULATED LOADS
 ACCORDING TO TYPE AND # OF NAILS USED.
 16-SOME CONNECTORS ARE MISSING ON ROOF
 FRAMING PLAN. SPECIFY AS REQUIRED.
 17-CONNECTOR TC-5 DOESN'T RESIST UPLIFT
 LOADS CALCULATED ON ROOF PLAN. REVISE
 AS REQUIRED.
 18-ROOF SHEATHING & NAILING NOTE ON DWG
 S3, SECTION 4 OF S3 AND DIAPHRAGM
 SCHEDULE HAVE DIFFERENT SPECS.
 **NOTE: KEEP IN MIND THAT FOR MEAN ROOF
 HEIGHT BET. 25' & 35' NEED TO USE 8D
 RING SHANK MIN. AS REQUIRED BY TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 19-SHOW NAILING ZONES IN ROOF FRAMING
 PLAN. SEE TABLE 2306.1 CITY AMENDMENTS
 20-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON FL. PLAN & EXT. ELEVATION
 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 22-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ATTACHMENT OF DOUBLE 2X BUCK FOR ENTRY
 DOOR INSTALLATION. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 23-UPDATE DWG C-1: FOUNDATION NOTE #1
 STILL CALLS FOR 0.004 MIL VISQUEEN.
 NEED 0.006 MIL MIN. SEC. 1909.2 FBC.
  
  
 NOTE:
 EXTERIOR ELEVATIONS ON SHEET A-4 ARE
 NOT SHOWN ON 1/4" SCALE.