2002-09-05 00:00:00 | SECOND CHECKLIST: |
| 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR |
| EXTERIOR MASONRY WALL WITH VERTICAL |
| REINFORCEMENT @ 8'-0"O.C. TIED TO THE |
| SINGLE BOND BEAM TO VERIFY FOR LATERAL |
| STABILITY (SEC. 2105 FBC 2001) AND |
| LATERAL SUPPORT (SEC. 2107 FBC 2001). |
| 2-A)PROVIDE COMPLETE DETAILS/ SPECS FOR |
| INSTALLATION OF ALL FRONT GABLE END |
| TRUSSES SHOWING HOW ARE THEY STRUCTU- |
| RALLY CONTINUOUS. SEE SEC. 2313 FBC. |
| B)CLARIFY WHY BLOCKING AT FRONT GABLE |
| ENDS IS ONLY SHOWN AS PARTIAL BLOCKING |
| AND NOT ALL THE WAY TO THE ENDS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 3-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 4-SHEET A-1: UPDATE NOTE #6. FPC 2001. |
| 5-FLOOR PLAN CALLS FOR SEC. A/A3. IS IT |
| B/A-3?. REVISE AS REQUIRED. |
| 6-WINDOW "E" IN BATHROOM #2 TO BE SAFETY |
| GLASS. SEC. 2405.2.1 FBC 2001. |
| 7-SHEET A4: REVISE FOOTING DIMENSIONS TO |
| MATCH FOUNDATION PLAN. |
| 8-SHEET S1: STRUCTURAL NOTE #1 CALLS FOR |
| 2000PSF, WHILE SOIL STATEMENT CALLS |
| FOR 2500PSF SOIL BEARING CAPACITY. |
| REVISE AS REQUIRED. |
| 9-SHEET S2: A)REVISE NOTE #2. RTPGA820 |
| STRAP IS DONE BY SEMCO WHICH IS OUT OF |
| BUSINESS. SEE USP CATALOGUE TO SPECIFY |
| PROPER CONNECTOR. |
| B)DETAIL A/S-2.1 TO READ A/S2. THERE IS |
| NOT SHEET S.2.1. REVISE AS REQUIRED. |
| 10-THERE IS NOT CONNECTOR DETAIL A/S2 |
| REFERENCED ON ROOF FRAMING PLAN. |
| 11-IDENTIFY ROOF NAILING ZONES IN ROOF |
| FRAMING PLAN. TABLE 2306.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 12-PROVIDE PRODUCT APPROVAL FOR GARAGE |
| SIDE DOOR. |
| 13-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS OR APPLY FORA |
| SEPARATE PERMIT. SEE CITY IMPLEMENTA- |
| TION STANDARD FOR HURRICANE MISSILE |
| IMPACT PROTECTION. |
| 14-SHEET S2: A)COLUMNS SPECIFIED ON |
| ELEVATION "A" DON'T MATCH FOUNDATION |
| PLAN. REVISE AS REQUIRED. |
| B)WHERE IS SECTION 1/S2? |
| 15-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| ARCHED WINDOW SHOWING 2X BUCK. |
| **NOTE: NEED DETAIL FOR ARCHED FRAMED |
| AREA ANDFOR ATTACHMENT TO MASONRY. |
| SEE EXTERIOR ELEVATION. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 16-PROVIDE GENERAL SPECIFICATIONS FOR |
| FIREBLOCKING AT ALL CONCEALED SPACES |
| AS REQUIRED BY SEC. 2305.1.4 FBC 2001. |
| 17-SEE PRODUCT APPROVAL FOR GARAGE DOORS |
| FOR STRUCTURAL BUCK SPECIFICATIONS AND |
| REVISE DETAIL AS REQUIRED. |
| **NOTE: SPECIFY WASHERS SIZE. SECTION |
| 104.2.1.2 CITY EMENDMENTS TO FBC 2001. |