2002-09-05 00:00:00SECOND CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 EXTERIOR MASONRY WALL WITH VERTICAL
 REINFORCEMENT @ 8'-0"O.C. TIED TO THE
 SINGLE BOND BEAM TO VERIFY FOR LATERAL
 STABILITY (SEC. 2105 FBC 2001) AND
 LATERAL SUPPORT (SEC. 2107 FBC 2001).
 2-A)PROVIDE COMPLETE DETAILS/ SPECS FOR
 INSTALLATION OF ALL FRONT GABLE END
 TRUSSES SHOWING HOW ARE THEY STRUCTU-
 RALLY CONTINUOUS. SEE SEC. 2313 FBC.
 B)CLARIFY WHY BLOCKING AT FRONT GABLE
 ENDS IS ONLY SHOWN AS PARTIAL BLOCKING
 AND NOT ALL THE WAY TO THE ENDS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-SHEET A-1: UPDATE NOTE #6. FPC 2001.
 5-FLOOR PLAN CALLS FOR SEC. A/A3. IS IT
 B/A-3?. REVISE AS REQUIRED.
 6-WINDOW "E" IN BATHROOM #2 TO BE SAFETY
 GLASS. SEC. 2405.2.1 FBC 2001.
 7-SHEET A4: REVISE FOOTING DIMENSIONS TO
 MATCH FOUNDATION PLAN.
 8-SHEET S1: STRUCTURAL NOTE #1 CALLS FOR
 2000PSF, WHILE SOIL STATEMENT CALLS
 FOR 2500PSF SOIL BEARING CAPACITY.
 REVISE AS REQUIRED.
 9-SHEET S2: A)REVISE NOTE #2. RTPGA820
 STRAP IS DONE BY SEMCO WHICH IS OUT OF
 BUSINESS. SEE USP CATALOGUE TO SPECIFY
 PROPER CONNECTOR.
 B)DETAIL A/S-2.1 TO READ A/S2. THERE IS
 NOT SHEET S.2.1. REVISE AS REQUIRED.
 10-THERE IS NOT CONNECTOR DETAIL A/S2
 REFERENCED ON ROOF FRAMING PLAN.
 11-IDENTIFY ROOF NAILING ZONES IN ROOF
 FRAMING PLAN. TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.
 12-PROVIDE PRODUCT APPROVAL FOR GARAGE
 SIDE DOOR.
 13-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FORA
 SEPARATE PERMIT. SEE CITY IMPLEMENTA-
 TION STANDARD FOR HURRICANE MISSILE
 IMPACT PROTECTION.
 14-SHEET S2: A)COLUMNS SPECIFIED ON
 ELEVATION "A" DON'T MATCH FOUNDATION
 PLAN. REVISE AS REQUIRED.
 B)WHERE IS SECTION 1/S2?
 15-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOW SHOWING 2X BUCK.
 **NOTE: NEED DETAIL FOR ARCHED FRAMED
 AREA ANDFOR ATTACHMENT TO MASONRY.
 SEE EXTERIOR ELEVATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 17-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 FOR STRUCTURAL BUCK SPECIFICATIONS AND
 REVISE DETAIL AS REQUIRED.
 **NOTE: SPECIFY WASHERS SIZE. SECTION
 104.2.1.2 CITY EMENDMENTS TO FBC 2001.