Plan Review Notes
Plan Review Notes For Permit 02070030
Permit Number 02070030
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-23 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 EXTERIOR MASONRY WALL WITH VERTICAL
 REINFORCEMENT AT 8'-0"O.C. TIED TO THE
 BOND BEAM TO VERIFY FOR LATERAL STABI-
 LITY (SEC. 2105 FBC 2001) AND LATERAL
 SUPPORT (SEC. 2107 FBC).
 2-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONSTRUCTION OF GABLE END TRUSSES AT
 FRONT OF ELEVATION SHOWING HOW ARE THE
 GABLE ENDS STRUCTURALLY CONTINUOUS.
 SEE SEC. 2313.4 FBC 2001.
 **NOTE: CLARIFY WHY BLOCKING AT FRONT
 GABLE ENDS IS SHOWN ONLY PARTIALLY
 AND NOT ALL THE WAY TO THE ENDS OF
 GABLE ENDS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-DWG C-1: REVISE NOTE #1. NEED 0.006
 MIL VISQEEN MIN. SEC. 1909.2 FBC 2001.
 5-SPECIFY INTERNAL PRESSURE COEFFICIENT
 AS REQ'D BY SEC. 1606.1.7 FBC 2001.
 6-SHEET A-1: UPDATE GENERAL NOTE #6.
 USE FPC 2001.
 7-THERE IS NOT SECTION A/A-3. IT SHOULD
 BE SECTION B/A-3. REVISE AS REQUIRED.
 8-PROVIDE SOIL TEST REPORT.
 9-WINDOW (E) IN BATHROOM #2 TO BE SAFETY
 GLASS. SEC. 2405.2.1 FBC 2001.
 10-SHEET A-4: REVISE FOOTING DIMENSIONS
 TO MATCH FOUNDATION PLAN.
 11-SHEET S-1: STRUCTURAL NOTE #1 CALLS
 FOR 2000PSF. SOIL STATEMENT CALLS FOR
 2500 PSF SOIL BEAR'G CAPACITY. CLARIFY
 12-SHEET S-3: A)REVISE/UPDATE NOTE #3
 TO FBC 2001 FOR 140MPH.
 B)NOTE#3: SEMCO IS OUT OF BUSINESS.
 REVISE STRAP RTPGA820.
 13-SHEET S-2: DETAIL A/S-2.1 TO READ
 A/S-2. THERE IS NOT S-2.1 DWG.
 14-THERE IS NOT CONNECTOR DETAIL A/S2 AS
 REFERENCED ON ROOF FRAMING PLAN.
 15-ENERGY CALCULATIONS: A)REVISE UNDER
 ATTIC AREA. SEE SEC. 602.1ABC.1.2 OF
 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO SIGN AND DATE BOTTOM
 OF ENERGY CALCS FORM.
 16-PROVIDE ROOF AND WALL SHEATHING
 SCHEDULE. TABLE 2306.1 CITY AMENDMENTS
 TO FBC 2001.
 **NOTE: IDENTIFY ROOF NAILING ZONES ON
 ROOF PLAN.
 17-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 18-PROVIDE PRODUCT APPROVAL FOR DOORS,
 WINDOWS AND WINDOW MULLIONS.
 19-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM PANELS OR APPLY FOR SEPARATE
 PERMIT AS REQUIRED BY CITY IMPLEMENTA-
 TION STANDARD FOR HURRICANE MISSILE
 IMPACT PROTECTION.
 20-SECTIONS 6 & 7 ON SHEET S-2: SPECIFY
 ALL CONNECTORS AND CLARIFY IF TRUSSES
 ARE BEARING ONM THE TOP OR BOTTOM
 CHORD. SEC. 104.2.1.2 CITY AMENDMENTS.
 21-SHEET S-2: A)COLUMNS SPECIFIED ON
 ELEVATION "A" DON'T MATCH FOUNDATION
 PLAN.
 B)WHERE IS SECTION 1/S2?.
 22-SHEET A-1: ATTIC ACCESS IS 36". SEE
 SEC. 2309.6 FBC 2001. REVISE NOTE #7.
 23-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOW SHOWING 2X BUCK.
 **NOTE: NEED DETAIL FOR MASONRY AND WOOD
 FRAMING. SEE EXTERIOR ELEVATION.
 24-SHEET A-4: A)SPECIFY FIREBLOCKING ON
 SECTION 1/A4. SEC. 2305.1.4 FBC 2001.
 B)PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 25-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 FOR STRUCTURAL BUCK SPECIFICATIONS AND
 REVISE DETAIL AS REQUIRED.