2002-08-29 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 EXTERIOR MASONRY WALL WITH VERTICAL
 REINFORCEMENT AT 8'-0"O.C. TIED TO THE
 SINGLE BOND BEAM TO CLARIFY FOR LATE-
 RAL STABILITY (SEC. 2105 FBC 2001) AND
 LATERAL SUPPORT (SEC. 2107 FBC 2001).
 2-PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF GABLE END TRUSSES AT
 FRONT ELEVATION.SEE SEC. 2313 FBC.
 **CLARIFY WHY BLOCKING AT FRONT GABLES
 IS SHOWN PARTIALLY AND NOT ALL THE WAY
 DOWN TO THE ENDS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-SHEET S2: CONNECTOR RT820 ON NOTE #2
 IS NOT DONE BY USP. REVISE AS REQ'D.
 4-COLUMNS SPECIFIED ON ELEVATION A OF S2
 DON'T MATCH FOUNDATION PLAN. REVISE.
 5-WHERE IS SEC. 1/S2?. SEE ROOF PLAN.
 6-ENERGY CALCULATIONS SUBMITTED ARE
 MISSING BOTTOM OF PAGE. PROVIDE TWO
 COPIES & OWNER/AGENT TO SIGN AND DATE.
 7-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 **PRODUCT APPROVAL SUBMITTED REQUIRES
 ENGINEER TO SIGN AND SEAL THE DRAWINGS
 AND PROVIDE ADDITIONAL ENGINEERING FOR
 CERTAIN MOUNTING CONDITIONS.
 **ALSO, VERIFY THAT KEY PLAN AND INSTA-
 LLATION SCHEDULE MATCH DWGS SUBMITTED.
 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOW.
 **DETAIL PROVIDED FOR ARCHED OPENINGS
 DOESN'T APPLY BECAUSE 1X BUCK WILL NOT
 SUPPORT THE WINDOW.
 **NEED DETAIL FOR FRAMED OPENING AND
 MASONRY WALL. SEE EXT. ELEVATIONS.
 9-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEE SEC. 2305.1.4 FBC 2001.
 10-SEE PRODUCT APPROVAL FOR GARAGE DOOR
 BUCK REQUIREMENTS AND REVISE DETAIL AS
 REQUIRED.
 11-WINDOW E IN BATHROOM #2 IS REQUIRED
 TO HAVE SAFETY GLASS. SEC. 2405.2 FBC.
 12-UPDATE TRUSS CONNECTOR TO MATCH USP
 ENGINEERED CALCULATIONS. PROVIDE
 ENGINEERING CALCS FOR LOADS DIFFERENT
 THAN THOSE SPECIFIED BY USP.
 **NOTE: NEED 1 3/4" PENETRATION INTO THE
 WOOD MEMBER WHEN USING 10D NAILS.
 13-PROVIDE COMPLETE DETAILS AND SPECS
 FOR INSTALLATION OF PRECAST LINTELS AT
 REAR PORCH. SPECIFY HOW IS COLUMN RE-
 INFORCEMENT CONNECTED TO THE LINTEL
 AND HOW ARE THE LINTELS TIED ONE
 ANOTHER TO ACHIEVE THE CONTINUITY OF
 THE BEAM AT THE PORCH AREA. AND HOW IS
 THE LINTEL ATTACHED TO MASONRY WALL.
 SEC. 104.2.1.2 CITY AMENDMENTS.
 14-REVISE LINTEL SCHEDULE TO MATCH THE
 OPENINGS SHOWN ON FOUNDATION PLAN.
 EG: CHECK DIMENSIONS AT REAR PORCH.
 **WHY IS CENTER LINTEL L-11 @ REAR PORCH
 LOCATED AT 12'-0"?.
 **CLARIFY WHAT IS 8F20-1B SPECIFIED ON
 LINTEL # L-17.
 15-PROVIDE DETAILS & SPECS FOR PRIVACY
 WALL AT FRONT AND ZERO LOT LINE SIDE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-PROVIDE PRODUCT APPROVAL FOR:
 A)DOUBLE FRENCH DOORS WITH SIDELITES
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 B)GARAGE DOORS
 17-SHEET A-2: KEY NOTE #4 DOESN'T APPLY
 FOR FRAMING AT ARCHED OPENINGS.