2002-08-29 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR |
| EXTERIOR MASONRY WALL WITH VERTICAL |
| REINFORCEMENT AT 8'-0"O.C. TIED TO THE |
| SINGLE BOND BEAM TO CLARIFY FOR LATE- |
| RAL STABILITY (SEC. 2105 FBC 2001) AND |
| LATERAL SUPPORT (SEC. 2107 FBC 2001). |
| 2-PROVIDE COMPLETE DETAILS/SPECS FOR |
| INSTALLATION OF GABLE END TRUSSES AT |
| FRONT ELEVATION.SEE SEC. 2313 FBC. |
| **CLARIFY WHY BLOCKING AT FRONT GABLES |
| IS SHOWN PARTIALLY AND NOT ALL THE WAY |
| DOWN TO THE ENDS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 3-SHEET S2: CONNECTOR RT820 ON NOTE #2 |
| IS NOT DONE BY USP. REVISE AS REQ'D. |
| 4-COLUMNS SPECIFIED ON ELEVATION A OF S2 |
| DON'T MATCH FOUNDATION PLAN. REVISE. |
| 5-WHERE IS SEC. 1/S2?. SEE ROOF PLAN. |
| 6-ENERGY CALCULATIONS SUBMITTED ARE |
| MISSING BOTTOM OF PAGE. PROVIDE TWO |
| COPIES & OWNER/AGENT TO SIGN AND DATE. |
| 7-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS UNDER A SEPARATE |
| PERMIT. CITY IMPLEMENTATION STANDARD |
| FOR HURRICANE MISSILE IMPACT PROTECT'N |
| **PRODUCT APPROVAL SUBMITTED REQUIRES |
| ENGINEER TO SIGN AND SEAL THE DRAWINGS |
| AND PROVIDE ADDITIONAL ENGINEERING FOR |
| CERTAIN MOUNTING CONDITIONS. |
| **ALSO, VERIFY THAT KEY PLAN AND INSTA- |
| LLATION SCHEDULE MATCH DWGS SUBMITTED. |
| 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ARCHED WINDOW. |
| **DETAIL PROVIDED FOR ARCHED OPENINGS |
| DOESN'T APPLY BECAUSE 1X BUCK WILL NOT |
| SUPPORT THE WINDOW. |
| **NEED DETAIL FOR FRAMED OPENING AND |
| MASONRY WALL. SEE EXT. ELEVATIONS. |
| 9-PROVIDE GENERAL SPECIFICATIONS FOR |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEE SEC. 2305.1.4 FBC 2001. |
| 10-SEE PRODUCT APPROVAL FOR GARAGE DOOR |
| BUCK REQUIREMENTS AND REVISE DETAIL AS |
| REQUIRED. |
| 11-WINDOW E IN BATHROOM #2 IS REQUIRED |
| TO HAVE SAFETY GLASS. SEC. 2405.2 FBC. |
| 12-UPDATE TRUSS CONNECTOR TO MATCH USP |
| ENGINEERED CALCULATIONS. PROVIDE |
| ENGINEERING CALCS FOR LOADS DIFFERENT |
| THAN THOSE SPECIFIED BY USP. |
| **NOTE: NEED 1 3/4" PENETRATION INTO THE |
| WOOD MEMBER WHEN USING 10D NAILS. |
| 13-PROVIDE COMPLETE DETAILS AND SPECS |
| FOR INSTALLATION OF PRECAST LINTELS AT |
| REAR PORCH. SPECIFY HOW IS COLUMN RE- |
| INFORCEMENT CONNECTED TO THE LINTEL |
| AND HOW ARE THE LINTELS TIED ONE |
| ANOTHER TO ACHIEVE THE CONTINUITY OF |
| THE BEAM AT THE PORCH AREA. AND HOW IS |
| THE LINTEL ATTACHED TO MASONRY WALL. |
| SEC. 104.2.1.2 CITY AMENDMENTS. |
| 14-REVISE LINTEL SCHEDULE TO MATCH THE |
| OPENINGS SHOWN ON FOUNDATION PLAN. |
| EG: CHECK DIMENSIONS AT REAR PORCH. |
| **WHY IS CENTER LINTEL L-11 @ REAR PORCH |
| LOCATED AT 12'-0"?. |
| **CLARIFY WHAT IS 8F20-1B SPECIFIED ON |
| LINTEL # L-17. |
| 15-PROVIDE DETAILS & SPECS FOR PRIVACY |
| WALL AT FRONT AND ZERO LOT LINE SIDE. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 16-PROVIDE PRODUCT APPROVAL FOR: |
| A)DOUBLE FRENCH DOORS WITH SIDELITES |
| SINGLE ASSEMBLY AS SHOWN ON PLANS. |
| B)GARAGE DOORS |
| 17-SHEET A-2: KEY NOTE #4 DOESN'T APPLY |
| FOR FRAMING AT ARCHED OPENINGS. |