2002-08-15 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) NOTE 1 UNDER FOUNDATION NOTES ON C-1 |
| CALLS FOR 0.004 VISQUEEN. PLEASE CORRECT |
| 6 MIL POLY IS REQUIRED. SEE FBC 1909.2. |
| |
| 3) PLEASE REVISE GENERAL NOTE #6 TO |
| REFERENCE THE 2001 FLORIDA PLUMBING CODE |
| |
| 4) GENERAL NOTE #13 IS ILLEGIBLE. |
| |
| 5) THERE IS NO SECTION A ON A-3 AS |
| REFERENCEDON A-1. SECTION B ON A-3 |
| APPEARS TO BE MISLABELED. PLEASE CORRECT |
| |
| 6) PROVIDE SOIL BEARING TEST REPORT PER |
| FBC 1804.2.2. A SIGNED AND SEALED COPY |
| TO BE SUBMITTED FOR PUBLIC RECORD. |
| |
| 7) THE WINDOW (E) IN BATHROOM #2 IS |
| REQUIRED TO BE SAFETY GLASS PER FBC |
| SECTION 2405.2.1 (2). |
| |
| 8) THE FOOTINGS ARE SHOWN AS 18" THICK |
| ON A-4 AND 16" THICK ON S-1. PLEASE |
| CORRECT. |
| |
| 9) THE STRUCTURAL NOTES ON S-1 INDICATE |
| THAT THE FOOTINGS ARE DESIGNED FOR |
| ALLOWABLE SOIL BEARING PRESSURE OF |
| 2000 PSF AND SOIL STATEMENT ON SAME |
| SHEET HAS 2500 PSF. PLEASE CLARIFY. |
| |
| 10) NOTE 3 ON S-2 STATES THAT TRUSS |
| LOADS WERE CALCULATED BASED ON 97 SBC |
| 110 MPH WIND VELOCITY. PLEASE CORRECT TO |
| 2001 FBC 140 MPH WIND VELOCITY. |
| |
| 11) THE RTPGA820 ON S-2 IS A SEMCO STRAP |
| SEMCO IS NO LONGER IN BUSINESS. PLEASE |
| SPECIFY A COMPARABLE USP OR SIMPSON |
| ANCHOR. |
| |
| 12) ON SHEET S-2 REFERENCE IS MADE TO |
| A ON S-2.3. THERE IS NO SHEET S-2.3. |
| PLEASE CORRECT. |
| |
| 13) INDICATE THE CEILING MATERIALS FOR |
| THE COVERED PORCH AND ENTRY. |
| |
| 14) THE TWO MIDDLE COLUMNS AT THE REAR |
| COVERED PORCH ARE MISLABELED. THEY |
| SHOULD BE LABELED FC1 COLUMNS. |
| |
| 15) THE 10'-6" L-10 LINTELS ON SHEET S-1 |
| CAN NOT SPAN THE 11'-6" BETWEEN THE |
| COLUMNS AT THE REAR PORCH AS INDICATED |
| ON THE PLANS. PLEASE CORRECT. |
| |
| 16) THERE IS NO DETAIL A ON S-2 AS |
| REFERENCED ON S-2. |
| |
| 17) THE AREA UNDER ATTIC ON THE ENERGY |
| CALCS. IS NOT CORRECT. IT DOES NOT |
| INCLUDE THE ADDITIONAL AREA CREATED BY |
| THE VAULTED CEILING. PLEASE CORRECT. |
| |
| 18) PROVIDE A DIAPHRAGM NAILING SCHEDULE |
| AND IDENTIFY THE ROOF NAILING ZONES PER |
| CHAPTER 23 OF THE CITY AMENDMENTS TO THE |
| 2001 FBC. |
| |
| 19) FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE ON PLANS THAT WWF WILL |
| BE SUPPORTED AS REQUIRED. |
| |
| 20) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - DOUBLE FRENCH DOORS WITH SIDELITES |
| - SINGLE HUNG WINDOWS (COVER SHEET IS |
| DIFFERENT FROM THE REST OF THE PAGES) |
| - LARGE ARCH TOP FIXED GLASS WINDOW AT |
| REAR ABOVE FRENCH DOOR |
| - STRUCTURAL MULLIONS |
| |
| 21) STORM PANELS: THE DIMENSIONS ON THE |
| KEY PLAN FOR OPENING #7 ARE INCORRECT. |
| THE SHUTTER WIDTH FOR OPENING #8 IS |
| TO SHORT. PLEASE CORRECT. |
| |
| 22) THE ANCHORS FOR THE TRUSSES SHOWN IN |
| SECTIONS 6 AND 7 ON S-2 ARE NOT |
| SPECIFIED. HOW ARE THE BOTTOM CORDS OF |
| THESE TRUSSES ANCHORED? ARE THE BEARING |
| POINTS OF THESE TRUSSES THE TOP CORD? |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |