Plan Review Notes
Plan Review Notes For Permit 02070027
Permit Number 02070027
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-15 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) NOTE 1 UNDER FOUNDATION NOTES ON C-1
 CALLS FOR 0.004 VISQUEEN. PLEASE CORRECT
 6 MIL POLY IS REQUIRED. SEE FBC 1909.2.
  
 3) PLEASE REVISE GENERAL NOTE #6 TO
 REFERENCE THE 2001 FLORIDA PLUMBING CODE
  
 4) GENERAL NOTE #13 IS ILLEGIBLE.
  
 5) THERE IS NO SECTION A ON A-3 AS
 REFERENCEDON A-1. SECTION B ON A-3
 APPEARS TO BE MISLABELED. PLEASE CORRECT
  
 6) PROVIDE SOIL BEARING TEST REPORT PER
 FBC 1804.2.2. A SIGNED AND SEALED COPY
 TO BE SUBMITTED FOR PUBLIC RECORD.
  
 7) THE WINDOW (E) IN BATHROOM #2 IS
 REQUIRED TO BE SAFETY GLASS PER FBC
 SECTION 2405.2.1 (2).
  
 8) THE FOOTINGS ARE SHOWN AS 18" THICK
 ON A-4 AND 16" THICK ON S-1. PLEASE
 CORRECT.
  
 9) THE STRUCTURAL NOTES ON S-1 INDICATE
 THAT THE FOOTINGS ARE DESIGNED FOR
 ALLOWABLE SOIL BEARING PRESSURE OF
 2000 PSF AND SOIL STATEMENT ON SAME
 SHEET HAS 2500 PSF. PLEASE CLARIFY.
  
 10) NOTE 3 ON S-2 STATES THAT TRUSS
 LOADS WERE CALCULATED BASED ON 97 SBC
 110 MPH WIND VELOCITY. PLEASE CORRECT TO
 2001 FBC 140 MPH WIND VELOCITY.
  
 11) THE RTPGA820 ON S-2 IS A SEMCO STRAP
 SEMCO IS NO LONGER IN BUSINESS. PLEASE
 SPECIFY A COMPARABLE USP OR SIMPSON
 ANCHOR.
  
 12) ON SHEET S-2 REFERENCE IS MADE TO
 A ON S-2.3. THERE IS NO SHEET S-2.3.
 PLEASE CORRECT.
  
 13) INDICATE THE CEILING MATERIALS FOR
 THE COVERED PORCH AND ENTRY.
  
 14) THE TWO MIDDLE COLUMNS AT THE REAR
 COVERED PORCH ARE MISLABELED. THEY
 SHOULD BE LABELED FC1 COLUMNS.
  
 15) THE 10'-6" L-10 LINTELS ON SHEET S-1
 CAN NOT SPAN THE 11'-6" BETWEEN THE
 COLUMNS AT THE REAR PORCH AS INDICATED
 ON THE PLANS. PLEASE CORRECT.
  
 16) THERE IS NO DETAIL A ON S-2 AS
 REFERENCED ON S-2.
  
 17) THE AREA UNDER ATTIC ON THE ENERGY
 CALCS. IS NOT CORRECT. IT DOES NOT
 INCLUDE THE ADDITIONAL AREA CREATED BY
 THE VAULTED CEILING. PLEASE CORRECT.
  
 18) PROVIDE A DIAPHRAGM NAILING SCHEDULE
 AND IDENTIFY THE ROOF NAILING ZONES PER
 CHAPTER 23 OF THE CITY AMENDMENTS TO THE
 2001 FBC.
  
 19) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 PLEASE INDICATE ON PLANS THAT WWF WILL
 BE SUPPORTED AS REQUIRED.
  
 20) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE FRENCH DOORS WITH SIDELITES
 - SINGLE HUNG WINDOWS (COVER SHEET IS
 DIFFERENT FROM THE REST OF THE PAGES)
 - LARGE ARCH TOP FIXED GLASS WINDOW AT
 REAR ABOVE FRENCH DOOR
 - STRUCTURAL MULLIONS
  
 21) STORM PANELS: THE DIMENSIONS ON THE
 KEY PLAN FOR OPENING #7 ARE INCORRECT.
 THE SHUTTER WIDTH FOR OPENING #8 IS
 TO SHORT. PLEASE CORRECT.
  
 22) THE ANCHORS FOR THE TRUSSES SHOWN IN
 SECTIONS 6 AND 7 ON S-2 ARE NOT
 SPECIFIED. HOW ARE THE BOTTOM CORDS OF
 THESE TRUSSES ANCHORED? ARE THE BEARING
 POINTS OF THESE TRUSSES THE TOP CORD?
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202