Plan Review Notes
Plan Review Notes For Permit 02061879
Permit Number 02061879
Review Stop B
Sequence Number 2
Notes
Date Text
2003-03-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 *NOTE*: A HISTORIC HOLD WAS PUT ON THIS
 PROPERTY ON 2/21/03.ANY CHANGE IN THE
 SCOPE OF WORK WILL REQUIRE SUBMITTAL OF
 PLANS FOR APPROVAL BY HISTORIC.CONTACT
 SHERRY PILAND ON (561) 659 8031 EXT 8362
  
 1) THE PROPOSED 'REVISIONS' ARE OUTSIDE
 THE SCOPE OF THE ISSUED PERMIT, WHICH
 ONLY COVERS STRUCTURAL REPAIRS TO THE
 EXISTING RESIDENCE.A SEPARATE PERMIT
 APPLICATION, WITH ARCHITECTURAL AND/OR
 STRUCTURAL PLANS, WILL BE REQUIRED FOR
 THE NEW CAR PORT, FRONT AND REAR PORCHES
 AND NEW UTILITY ROOM. THE ELECTRICAL AND
 PLUMBING SUB-CONTRACTORS MUST 'SIGN-ON',
 OR SEPARATE SUB-PERMIT APPLICATIONS WILL
 BE REQUIRED.
  
 2) REPLACEMENT OF WINDOWS.THE SCOPE OF
 THE ISSUED PERMIT IS STRUCTURAL REPAIR.
 THIS WOULD NOT COVER GENERAL WINDOW
 REPLACEMENT.SUBMIT A COPY OF THE
 CONTRACT TOGETHER WITH A KEY PLAN AND
 SCHEDULE TO SHOW HOW MANY, AND WHICH,
 WINDOWS ARE TO BE REPLACED.
  
 3) THE SUBMITTED COPIES OF THE PREMDOR
 DOUBLE INSWING WOOD DOOR PRODUCT
 APPROVAL NOA# 01-1127.16 ARE MISSING
 DRAWING SHEET 1 OF 4.NOTE: THE LAYOUTS
 SUBMITTED WITH THE PROPOSED 'REVISION'
 DO NOT SHOW ANY DOUBLE INSWING DOOR.
 PLEASE CLARIFY.
  
 4) DRAWING SHEETS 1 THRU 3 OF 3, OF THE
 SOUTHEASTERN METALS MANUFACTURING STEEL
 STORM PANEL SHUTTER PRODUCT APPROVAL
 NOA# 02-0809.02 ARE NOT LEGIBLE DUE TO
 POOR COPY QUALITY.SUBMIT LEGIBLE
 COPIES.ALSO AN INSTALLATION SCHEDULE
 AND KEY PLAN SHALL BE SUBMITTED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499