2003-04-03 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS, RISER
 AND PANEL SCHEDULE. NOTES, MENTION 200A
 PANEL W/ 200A MCB AND THE REST SHOW 150A
 ???
  
 2)NOTE: PLAN SHOWS WHAT APPEARS TO BE
 A METER/MAIN COMBO AND RISER SHOWS A
 SEPARATE DISC?
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D/210-11C-3
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
 5)NOTE: PLEASE SEE NOTES ON PLANS, THEY
 MENTION ALL WORK TO BE DONE PER PALM
 BEACH COUNTY, PLEASE NOTE, WORK ADDRESS
 IS IN CITY OF WEST PALM BEACH.
  
 6)NOTE: PLEASE SIZE OCP FOR AHU PER
 424-3. SHOWN AS 50A, MIN FOR 10KW IS
 60A.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 PENINSULAR PER 210-52C-1,2,3,ETC.
 PLEASE NOTE, ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 PER 210-8-A-6, NOT JUST RECEPTS W/IN 6'
 OF SINK AS MENTIONED IN ELEC. NOTE #3.
  
 8)NOTE: PLEASE SEE MISSING SD AT THE
 BOTTOM OF STAIRS REQ`D PER NFPA-72
 8-1.4.2
  
 9)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL. SIZE PER 250-122
  
 10)NOTE: CLOSET LTS ARE SHOWN TOO CLOSE
 TO CLOTHES/STORAGE RACK PER 410-8
  
 PLEASE NOTE, PLANS WERE ORIG BROUGHT IN
 FOR MISC STRUCTURE REPAIRS, AND NOW
 ARE COMING IN W/ COMPLETE REDO OF P
 PLEASE ADJUST VALUE FOR SCOPEOF WORK
 NOW BEING DONE. PER 104.6.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  