2003-04-03 00:00:00 | **************** UNSAT *************** |
| |
| 1)NOTE: PLEASE CORRELATE PLANS, RISER |
| AND PANEL SCHEDULE. NOTES, MENTION 200A |
| PANEL W/ 200A MCB AND THE REST SHOW 150A |
| ??? |
| |
| 2)NOTE: PLAN SHOWS WHAT APPEARS TO BE |
| A METER/MAIN COMBO AND RISER SHOWS A |
| SEPARATE DISC? |
| |
| 3)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| BATH CIRCUIT(S) PER 210-52D/210-11C-3 |
| |
| 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS PER 210-12 ON PANEL |
| SCHEDULE. |
| 5)NOTE: PLEASE SEE NOTES ON PLANS, THEY |
| MENTION ALL WORK TO BE DONE PER PALM |
| BEACH COUNTY, PLEASE NOTE, WORK ADDRESS |
| IS IN CITY OF WEST PALM BEACH. |
| |
| 6)NOTE: PLEASE SIZE OCP FOR AHU PER |
| 424-3. SHOWN AS 50A, MIN FOR 10KW IS |
| 60A. |
| |
| 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| PENINSULAR PER 210-52C-1,2,3,ETC. |
| PLEASE NOTE, ALL OUTLETS SERVING KITCHEN |
| COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| PER 210-8-A-6, NOT JUST RECEPTS W/IN 6' |
| OF SINK AS MENTIONED IN ELEC. NOTE #3. |
| |
| 8)NOTE: PLEASE SEE MISSING SD AT THE |
| BOTTOM OF STAIRS REQ`D PER NFPA-72 |
| 8-1.4.2 |
| |
| 9)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR BETWEEN MAIN DISC |
| AND PANEL. SIZE PER 250-122 |
| |
| 10)NOTE: CLOSET LTS ARE SHOWN TOO CLOSE |
| TO CLOTHES/STORAGE RACK PER 410-8 |
| |
| PLEASE NOTE, PLANS WERE ORIG BROUGHT IN |
| FOR MISC STRUCTURE REPAIRS, AND NOW |
| ARE COMING IN W/ COMPLETE REDO OF P |
| PLEASE ADJUST VALUE FOR SCOPEOF WORK |
| NOW BEING DONE. PER 104.6.5 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |