2003-07-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 THE ORIGINAL APPLICATION WAS FOR
 STRUCTURAL REPAIRS AS PER THE DETAILS
 PROVIDED BY BOTKIN PARSSI & ASSOCIATES,
 P.E.THE SUBMITTED 'REVISION' IS FOR
 THE CONSTRUCTION OF A NEW UTILITY ROOM
 ADDITION AND NEW CAR PORT TO DETAILS
 PROVIDED BY A DIFFERENT ENGINEER, WALTER
 KARPINIA, P.E.THIS WILL REQUIRE THE
 SUBMITTAL OF A SEPARATE PERMIT
 APPLICATION WITH FEES BASED ON THE
 VALUE OF THE NEW WORK.THE PLANS HAVE
 NOT BEEN REVIEWED.THE ELECTRICAL AND
 PLUMBING SUB-CONTRACTORS MUST 'SIGN-ON',
 OR SEPARATE SUB-PERMIT APPLICATIONS WILL
 BE REQUIRED.
  
 REPLACEMENT OF WINDOWS.THE SCOPE OF
 THE ISSUED PERMIT IS STRUCTURAL REPAIR.
 THIS WOULD NOT COVER GENERAL WINDOW
 REPLACEMENT.SUBMIT A COPY OF THE
 CONTRACT TOGETHER WITH A KEY PLAN AND
 SCHEDULE TO SHOW HOW MANY, AND WHICH,
 WINDOWS ARE TO BE REPLACED.
  
 NOTE THAT THE LEFT ELEVATION REFERS TO
 THE FAMILY ROOM AS 'NEW WOOD ADDITION'.
 AMEND THE PLANS TO CLARIFY BEFORE
 SUBMITTAL.
  
 FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)