2002-07-03 00:00:00 | ************** UNSAT ************* | | | | 1)NOTE: PLEASE ALSO SEE COMMENTS ON | | PERMIT #02061859. | | PLEASE CORRELATE SUBMITTED PLANS AND | | 8 1/2X 14`S. | | | | 2)NOTE: PLEASE NOTE PLANS NEED MORE | | INFORMATION OF LAY OUT OF NEW OUTLETS | | PER UPS SCHEDULE. | | | | 3)NOTE: PLEASE NOTE MISSING INFORMATION | | FOR WIRE SIZES, CONDUIT SIZES ETC. | | | | 4)NOTE: PLEASE SUBMIT A COPY OF CONTRACT | | TO VERIFY VALUE FOR COMPLETE SCOPE OF | | WORK. PLEASE NOTE PER FAC/ FEES ARE | | BASED ON VALUE, INCLUDING ALL LABOR AND | | MATERIALS. INCLUDING ANY OWNER SUPPLIED | | EQUIPMENT IF HARDWIRED. | | 104.6.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|