Plan Review Notes For Permit 02061859 |
Permit Number |
02061859 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-03 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT TWO SETS OF | | PLANS WERE SUBMITTED.?? PLEASE ALSO NOTE | | RISER DIAGRAMS DO NOT CORRELATE. PLEASE | | NOTE 8 1/2X 14`S NEED MORE INFORMATION, | | IF THOSE ARE GOING TO BE USED. | | NEEDS CONDUIT, WIRE SIZES, AIC RATING | | FOR ALL NEW EQUIPMENT. | | | | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | FOR RELOCATIONOF FIRE ALARM DEVICES. | | | | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | DO NOT CORRELATE? | | | | MECH NOT TO BE REVIEW PER ELECTRICAL | | CONT.7/2/02 | | | | PLEASE SUBMIT AND CLARIFY PLANS AND | | SUBMIT INFORMATION FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|