2002-08-26 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061849
 ADD: 3093 BOLLARD RD
 CONT: INTELI HOMES
 TEL: (561)432-9022
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****BUILDING PROVISO*****
  
 1) TABLE 600 0 TO 3' FROM PROPERTY LINE,
 NO OPENINGS IN ZERO LOT LINE SIDE OF
 UNIT, GLASS BLOCK SHALL BE A FULL 1 HR.
 RATING, PROVIDE MANUFACTURERERS SPEC ON
 GLASS BLOCK BEFORE BUCK INSPECTION.
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.MISSING SCHEDULE & KEY PLAN
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 FAILURE TO PRODUCE A KEY PLAN AND ATTACH
 MENT SCHEDULE BEFORE BUCK INSPECTION
 SHALLRESULT IN REQUIRING A SEPERATE
 PERMIT FOR STORM SHUTTERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412