Plan Review Notes
Plan Review Notes For Permit 02061658
Permit Number 02061658
Review Stop P
Sequence Number 1
Notes
Date Text
2002-07-08 00:00:00PLUMBING PLAN REVIEW, DENIED. PES
 REVIWED FBC 2000
 (1) TYPE OF GAS, (LP OR NATURAL)
 (2) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 (3) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 502 THRU 506
 (4) INDICATE THE DELIVERY PRESSURE PSI
 PER FBC, SEC 402.2IF NATURAL GAS
 SPECIFY .5 PSI OR 2 PSI.
 (5) SUBMIT MANUFACTURE SHEETS FOR ALL
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC SEC 402.2
 (6) SHOW PLAN VIEW TO VERIFY LOCATION OF
 APPLIANCES,FBC SEC 104.2
 END OF COMMENTSPAUL SCHMITZ