2002-07-06 00:00:00PLAN DENIED
 1) NO SIZE ON DUCT TO BONUS ROOM
 2) NEED FRESH AIR CALCS ON PLAN
 3) CAN NOT HAVE R/A IN LAUNDRY ROOM
 PLAN REVIEW BY HAROLD MOSER