Plan Review Notes
Plan Review Notes For Permit 02061462
Permit Number 02061462
Review Stop M
Sequence Number 1
Notes
Date Text
2002-07-16 00:00:00PLAN/DENIED
 1) CHECK CFM.IN LIVING ROON A/C VENT
 2) CHECK MASTER BATH DUCT SIZE
 3) RETURN AIR DUCT MUST BE SAME SIZE AS
 SUPPLY DUCT.BEDROOM #2,MASTER BEDROOM
 SECTION 601.4 2001 MECHANICAL CODE
 4) CHECK A/C SIZE.TOTAL A/C AREA 1719 SF
 5) NEED FRESH AIR CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER