2002-07-03 00:00:001) SITE PLAN MUST SHOW ANY NEW OR
 EXISTING FIRE HYDRANT LOCATIONS.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 THE FIRE DEPARTMENT SPRINKLER CONNECTION
 MUST BE WITHIN 150 FEET FROM A FIRE
 HYDRANT.
  
 3) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON BACKFLOW DEVICE.
  
 4) TENANT SEPARATION WALLS ARE TO MEET
 FLORIDA BUILDING CODE REQUIREMENTS.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM
 TO BE CLASS A OR FULLY ADDRESSABLE.
  
 6) DUCT SMOKE DETECTORS ARE REQUIRED
 ON ALL AIR HANDLING UNITS 2000 CFM OR
 ABOVE.
  
 7) SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED FOR EACH TENANT FIT-UP
 PLANNED FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910