 BUILDING PLAN REVIEW
 PERMIT: 02061385
 ADD: 2301 CENTREPARK W DRIVE
 CONT: LEIGHTON MCGINN CO
 TEL: (561)863-4455
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL A-9 FLOODZONE BASE 13'+
 6" CITY CODE, MINIMUM 13'6", FINISH
 FLOOR & A/C PADS.
  
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 1503.4.4 PROTECTION AGAINST DECAY &
 TURMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A)WINDOWS
 B)MULLIONS
 C)DOORS, EXTERIOR
 D)ROOFING ASSEMBLIES
  
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
  
 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.
  
 SHEET A-3 DETAIL #3 FAN ROOF MOUNT
 DETAIL NO FASTENING INFO?
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLANS DO NOT INDI-
 CATE WITH STAMP FEES WERE PAID, RECEIPT
 FROM COUNTY IN PACKAGE?