Plan Review Notes
Plan Review Notes For Permit 02061278
Permit Number 02061278
Review Stop E
Sequence Number 2
Notes
Date Text
2002-08-06 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 THE GROUNDING ELECTRODE MUST BE
 CONNECTED AT THE FIRST MEANS OF
 DISCONNECT OR AT THE METER,NOT IN THE
 PANEL WHERE IT COULD PRODUCE A PARALLEL
 GROUND PATH WITH THE NEUTRAL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392