2002-08-30 00:00:00 | SECOND CHECKLIST: |
| 1-SECOND FLOOR FRAMING PLAN: REVISE DET. |
| 5/S3. CONNECTOR SPECIFIED IS A LIGHT |
| GAUGE PURLIN HANGER NOT A HANGER FOR |
| A GIRDER TRUSS. ALSO, USP HL210 HAS NO |
| UPLIFT CAPACITY. SEE USP CATALOGUE. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 2-DETAIL 5/S3: PROVIDE COMPLETE SPECS |
| FOR GABLE END INSTALLATION. SPECIFY |
| ALL CONNECTORS AND HOW IS THE TRUSS |
| ATTACHED TO PROVIDE CONTINUITY. SEE |
| SECTION 2313.4 FBC 2001. |
| ALSO, SEE TABLE 2306.1 CITY AMENDMENTS |
| TO FBC FOR NAIL TYPE AND SPACING. |
| (8D RING SHANK AT 25' MEAN ROOF HT.) |
| 3-REVISE TRUSS CONNECTOR SCHEDULE TO |
| MATCH PUBLISHED VALUES BY USP. |
| SCHEDULE WAS NOT PROPERLY REVISED. THE |
| NAIL TYPE WAS CHANGED TO 10DX1 1/2 BUT |
| VALUES GIVEN ARE FOR 10D NAILS. |
| **PROVIDE ACTUAL ENGINEERING CALCS FOR |
| UPLIFT VALUES NOT PUBLISHED BY USP. |
| 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 5-WINDOW BY ENTRY PORCH TO BE SHOWN AS |
| DOTTED LINES ON LEFT ELEVATION, SHEET |
| A-4. OTHERWISE, IT REPRESENTS THAT THE |
| WINDOW IS ON THE ZERO LOT LINE WALL. |
| 6-PROVIDE GENERAL SPECIFICATIONS FOR |
| REQUIRED FIREBLOCKING AT ALL CONCEALED |
| SPACES AS REQ'D BY SEC. 2305.1.4 FBC. |
| 7-PROVIDE COMPLETE AND CORRECT INFO. FOR |
| STORM SHUTTERS OR APPLY FOR SEPARATE |
| PERMIT. |
| **KEY PLAN & INSTALLATION SCHEDULE DON'T |
| MATCH PLANS. |
| **PRODUCT APPROVAL SUBMITTED REQUIRES |
| ENGINEER TO SIGN AND SEAL DRAWINGS AND |
| REQUIRES ADDITIONAL ENGINEERING FOR |
| SPECIFIC MOUNTING CONDITIONS. SEE |
| LIMITATIONS ON PAGE 4 OF 4 OF PRODUCT |
| APPROVAL REPORT. |
| 8-SHEET S3: ROOF SHEATHING SPECS SHOWN |
| IN SECTION 5 AND DIAPHRAGM SCHEDULE |
| DON'T MATCH. REVISE AS REQUIRED. |
| 9-GARAGE DOOR STRUCTURAL BUCK DETAIL: |
| SPECIFY LENGTH OF ANCHOR BOLTS AND |
| REQUIRED WASHER. SEC. 104.2.1.2 CITY |
| AMENDMENTS AND SEC. 1606 FBC 2001. |
| 10-DRAWINGS SUBMITTED SHOW GARAGE ON THE |
| RIGHT HAND SIDE, WHILE SURVEY SHOWS |
| GARAGE ON THE LEFT HAND SIDE. CLARIFY |
| TO AVOID CONFLICTS WITH ZONING. |