2002-08-29 00:00:00PASS/PRIVISO
 1) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 2) RETURN AIR DUCT MUST BE SAME SIZE OR
 LARGER THAN SUPPLY DUCT SECTION 601.4
 FBC.2001
 3) NEED FAN SHUT DOWN FOR FINAL
 4) NEED PROGRAMMABLE T.STAT FOR FINAL
 PLAN REVIEW BY HAROLD MOSER