Plan Review Notes For Permit 02061262 |
Permit Number |
02061262 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-08-29 00:00:00 | PASS/PRIVISO | | 1) NEED FRESH AIR CALCULATIONS FOR ROUGH | | INSPECTION | | 2) RETURN AIR DUCT MUST BE SAME SIZE OR | | LARGER THAN SUPPLY DUCT SECTION 601.4 | | FBC.2001 | | 3) NEED FAN SHUT DOWN FOR FINAL | | 4) NEED PROGRAMMABLE T.STAT FOR FINAL | | PLAN REVIEW BY HAROLD MOSER |
|