2002-08-20 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ENTRY DOORS SIZE TO PROVIDE THE
 32" MIN. CLEAR OPENING REQUIRED BY
 TABLE 1004 FBC 2001.
 3-WINDOW AT ENTRY PORCH EXCEEEDS MAX. %
 OF OPENINGS ALLOWED BY TABLE 600 FBC.
 4-SPECIFY FIREBLOCKING MATERIALS AND
 LOCATION AT STAIRS, INCLUDING AT TOP
 OF STAIRS. SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECS FOR REQ'D
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEEE SEC. 2305.1.4 FBC 2001.
 5-SPECIFY DRAFSTOPPING LOCATIONS AND
 MATERIAL @ 2ND FL. FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 **NOTE: FIRESTOPPING TO BE PLACED SO
 AREAS DON'T EXCEED 500 S.F.
 6-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 7-PROVIDE SOIL TEST REPORT.
 8-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SECTION 1909.3 FBC 2001.
 9-PROVIDE COMPLETE & CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
 10-PROVIDE PRODUCT APPROVALS FOR DOORS,
 WINDOWS AND WINDOW MULLIONS ASSEMBLIES
 AS SHOWN ON PLANS.
 11-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAILING TO BE BET. 34" & 38"
 MAX. SEE SEC. 1007.5.1 FBC 2001.
 12-2ND FLLOR FRAMING PLAN:
 REVISE/CLARIFY AND PROVIDE DETAIL FOR
 USING USP HL210 HANGERS FOR DOUBLE
 GIRDER TRUSSES RESTING ON THE MASONRY
 WALL BY THE 2 SIDES OF STAIRWAY. SEE
 CONNECTOR SPECS/SIZE ON USP CATALOGUE.
 13-DETAIL 4/S3 DOESN'T APPLY. NEED GABLE
 END DETAIL (SEE SEC. 2117 FBC). ALSO,
 ROOF FRAMING PLAN CALLS FOR SEC. 5/S3,
 NOT 4/S3. CLARIFY/REVISE AS REQUIRED.
 14-NOTE ON BUCKET DETAILS SHEET S2 CALLS
 FOR 1/4" WELDING. ALL THE DETAILS CALL
 FOR 3/16" WELDING. CLARIFY/REVISE.
 15-REVISE TRUSS CONNECTOR SCHEDULE:
 # OF NAILS AND UPLIFT LOADS SPECIFIED
 DON'T MATCH THOSE ON USP CATALOGUE.
 PROVIDE ENGINEERING CALCULATIONS FOR
 LOADS DIFFERENT THAN THOSE SPECIFIED
 ON USP CATALOGUE.
 **NOTE: SEE USP LIMITATIONS WHEN USING
 DOUBLE ANCHORS AND CONNECTORS ARE LESS
 THAN 8" APART.
 16-SOME CONNECTORS ARE NOT SPECIFIED ON
 ROOF FRAMING PLAN. SPECIFY THEM.
 17-REVISE CONNECTOR TC-5. IT DOESN'T
 RESIST THE UPLIFT LOADS CALCULATED ON
 ROOF FRAMING PLAN.
 18-ROOF SHEATHING NOTE (DWG S3), SECTION
 4 OF S3 AND DIAPHRAGM SCHEDULE HAVE
 DIFFERENT SPECS FOR ROOF SHEATHING
 FASTENERS. REVISE AS REQUIRED.
 19-SHOW NAILING ZONES IN ROOF FRAMING
 PLAN. SEE TABLE 2306.1 CITY AMENDMENTS
 TO FBC 2001.
 20-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON THE FLOOR PLAN AND ON EXT
 ELEVATION. REVISE AS REQUIRED.
 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 22-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ATTACHMENT OF DOUBLE 2X BUCK FOR ENTRY
 DOOR. SEC. 104.2.1.2 CITY AMENDMENTS.
 23-UPDATE DRAWING C-1 AS WELL.
  
 QUESTION?
 IS THERE ANY REASON WHY THESE PLANS ARE
 SHOWING GARAGE ON THE RIGHT HAND SIDE,
 BUT SURVEY SHOWS GARAGE ON THE OTHER
 SIDE?.(LOT 76 IS THE SAME MODEL AND ALL
 DWGS SHOW GARAGE ON LEFT HAND SIDE).