2002-08-20 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-REVISE ENTRY DOORS SIZE TO PROVIDE THE |
| 32" MIN. CLEAR OPENING REQUIRED BY |
| TABLE 1004 FBC 2001. |
| 3-WINDOW AT ENTRY PORCH EXCEEEDS MAX. % |
| OF OPENINGS ALLOWED BY TABLE 600 FBC. |
| 4-SPECIFY FIREBLOCKING MATERIALS AND |
| LOCATION AT STAIRS, INCLUDING AT TOP |
| OF STAIRS. SEC. 2305.1.4 FBC 2001. |
| **NOTE: PROVIDE GENERAL SPECS FOR REQ'D |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEEE SEC. 2305.1.4 FBC 2001. |
| 5-SPECIFY DRAFSTOPPING LOCATIONS AND |
| MATERIAL @ 2ND FL. FRAMING PLAN AS |
| REQUIRED BY SEC. 2305.2.2 FBC 2001. |
| **NOTE: FIRESTOPPING TO BE PLACED SO |
| AREAS DON'T EXCEED 500 S.F. |
| 6-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| 7-PROVIDE SOIL TEST REPORT. |
| 8-SPECIFY SPACING FOR WWM SUPPORTS. SEE |
| SECTION 1909.3 FBC 2001. |
| 9-PROVIDE COMPLETE & CORRECT INFORMATION |
| FOR STORM SHUTTERS OR APPLY FOR A |
| SEPARATE PERMIT. CITY IMPLEMENTATION |
| STANDARD FOR HURRICANE MISSILE IMPACT |
| PROTECTION. |
| 10-PROVIDE PRODUCT APPROVALS FOR DOORS, |
| WINDOWS AND WINDOW MULLIONS ASSEMBLIES |
| AS SHOWN ON PLANS. |
| 11-REVISE STAIR KEY NOTE #1. HEIGHT OF |
| STAIR HANDRAILING TO BE BET. 34" & 38" |
| MAX. SEE SEC. 1007.5.1 FBC 2001. |
| 12-2ND FLLOR FRAMING PLAN: |
| REVISE/CLARIFY AND PROVIDE DETAIL FOR |
| USING USP HL210 HANGERS FOR DOUBLE |
| GIRDER TRUSSES RESTING ON THE MASONRY |
| WALL BY THE 2 SIDES OF STAIRWAY. SEE |
| CONNECTOR SPECS/SIZE ON USP CATALOGUE. |
| 13-DETAIL 4/S3 DOESN'T APPLY. NEED GABLE |
| END DETAIL (SEE SEC. 2117 FBC). ALSO, |
| ROOF FRAMING PLAN CALLS FOR SEC. 5/S3, |
| NOT 4/S3. CLARIFY/REVISE AS REQUIRED. |
| 14-NOTE ON BUCKET DETAILS SHEET S2 CALLS |
| FOR 1/4" WELDING. ALL THE DETAILS CALL |
| FOR 3/16" WELDING. CLARIFY/REVISE. |
| 15-REVISE TRUSS CONNECTOR SCHEDULE: |
| # OF NAILS AND UPLIFT LOADS SPECIFIED |
| DON'T MATCH THOSE ON USP CATALOGUE. |
| PROVIDE ENGINEERING CALCULATIONS FOR |
| LOADS DIFFERENT THAN THOSE SPECIFIED |
| ON USP CATALOGUE. |
| **NOTE: SEE USP LIMITATIONS WHEN USING |
| DOUBLE ANCHORS AND CONNECTORS ARE LESS |
| THAN 8" APART. |
| 16-SOME CONNECTORS ARE NOT SPECIFIED ON |
| ROOF FRAMING PLAN. SPECIFY THEM. |
| 17-REVISE CONNECTOR TC-5. IT DOESN'T |
| RESIST THE UPLIFT LOADS CALCULATED ON |
| ROOF FRAMING PLAN. |
| 18-ROOF SHEATHING NOTE (DWG S3), SECTION |
| 4 OF S3 AND DIAPHRAGM SCHEDULE HAVE |
| DIFFERENT SPECS FOR ROOF SHEATHING |
| FASTENERS. REVISE AS REQUIRED. |
| 19-SHOW NAILING ZONES IN ROOF FRAMING |
| PLAN. SEE TABLE 2306.1 CITY AMENDMENTS |
| TO FBC 2001. |
| 20-DESIGN PRESSURES FOR ENTRY DOORS ARE |
| DIFFERENT ON THE FLOOR PLAN AND ON EXT |
| ELEVATION. REVISE AS REQUIRED. |
| 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| STRUCTURAL BUCK SPECS AND REVISE |
| DETAIL AS REQUIRED. |
| 22-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| ATTACHMENT OF DOUBLE 2X BUCK FOR ENTRY |
| DOOR. SEC. 104.2.1.2 CITY AMENDMENTS. |
| 23-UPDATE DRAWING C-1 AS WELL. |
| |
| QUESTION? |
| IS THERE ANY REASON WHY THESE PLANS ARE |
| SHOWING GARAGE ON THE RIGHT HAND SIDE, |
| BUT SURVEY SHOWS GARAGE ON THE OTHER |
| SIDE?.(LOT 76 IS THE SAME MODEL AND ALL |
| DWGS SHOW GARAGE ON LEFT HAND SIDE). |