Date |
Text |
2002-09-03 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-FLOOD ZONE A8: NEED TO PROVIDE THE |
| ELEVATION CERTIFICATE. |
| 2-PROVIDE COMPLETE UL LISTING AND SPECS |
| FOR 1 HR. FIRE RATED GLASS BLOCK. |
| REVISE DETAIL SEE UL SPECS. |
| **NOTE: GLASS BLOCK TO BE SAFTEY GLASS |
| IF UNIFORM FACE THICKNESS IS LESS THAN |
| 0.25". SEE SEC. 2405.2 FBC 2001. |
| **NOTE: PROVIDE LEGIBLE PRODUCT APPROVAL |
| AND DRAWINGS ALSO. |
| 3-WOOD COLUMN DETAILS: A)SPECIFY HOW |
| MUCH EMBEDMENT FOR 1/2" ANCHOR BOLTS. |
| B)CLEARLY IDENTIFY TOP CONNECTORS AND |
| CLARIFY HOW ARE STRAPS USED RESISTING |
| FOR LATERAL LOADS AND HOW ARE TO WOOD |
| MEMBERS RESTING ON THE COLUMN BEING |
| SUPPORTED BY THE METAL STRAPS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 4-PROVIDE SOIL TEST REPORT. |
| 5-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| **NOTE: NEED ORIGINAL SIGNED AND SEALED |
| DRAWINGS AS REQUIRED BY THE ENGINEER. |
| ALSO, NEED ADDITIONAL ENGINEERING FOR |
| CERTAIN MOUNTING CONDITIONS. SEE SHEET |
| 4 OF 4 OF PRODUCT APPROVAL REPORT. |
| 6-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| STRUCTURAL BUCK SPECIFICATIONS AND |
| REVISE DETAIL AS REQUIRED. |
| **NOTE: SPECIFY SIZE OF WASHER. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-SPECIFY FIREBLOCKING @ STAIRS INCLUD'G |
| AT TOP. SEE SEC. 2305.1.4 FBC 2001. |
| **NOTE: PROVIDE GENERAL SPECIFICATIONS |
| FOR FIREBLOCKING AT ALL CONCEALED |
| SPACES. SEE SEC. 2305.1.4 FBC 2001. |
| 8-PROVIDE STRUCTURAL FRAMING DETAIL FOR |
| INSTALLATION OF OVAL WINDOW. KEEP IN |
| MIND THAT NEED 2X BUCK FOR ATTACHMENT |
| OF WINDOW. SEC. 104.2.1.2 CITY AMENDM. |
| 9-REVISE STAIR KEY NOTE #1. HANDRAILS TO |
| BE BET. 34" AND 38". SEC. 107.5.1 FBC. |
| *NOTE: HANDRAILS & GUARDRAILS ARE NOT |
| THE SAME. |
| 10-REVISE TRUSS CONNECTOR SCHEDULE TO |
| MATCH USP PUBLISHED VALUES. OR PROVIDE |
| ENGINEERING CALCULATIONS FOR DIFFERENT |
| UPLIFT VALUES. NOTE: VALUES TO MATCH |
| TYPE OF NAIL USED. |
| 11-SHOW NAILING ZONES ON ROOF PLAN. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 12-ROOF PLAN: CLARIFY WHY THERE IS NOT |
| BLOCKING SHOWN ON INTERIOR GABLE END. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 13-DETAIL R19: SPECIFY ALL FASTENERS. |
| THERE IS NOT STRAP SPECIFIED ON ROOF |
| PLAN. ALSO, PROVIDE COMPLETE SPECS |
| SHOWING HOW IS TRUSS DESIGNED TO BE |
| CONTINUOUS AT LATERAL SUPPORT. SEE |
| SECTION 2117 AND 2313 FBC 2001. |
| **NOTE: ALSO, PROVIDE COMPLETE DETAIL/ |
| SPECS FOR INTERIOR GABLE END SHOWING |
| CONTINUITY AT LATERAL SUPPORT. SEC. |
| 2313 FBC 2001. |
| 14-PROVIDE FIRECUT REQUIREMENTS IN |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |