2002-09-03 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-FLOOD ZONE A8: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR 1 HR. FIRE RATED GLASS BLOCK.
 REVISE DETAIL SEE UL SPECS.
 **NOTE: GLASS BLOCK TO BE SAFTEY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2 FBC 2001.
 **NOTE: PROVIDE LEGIBLE PRODUCT APPROVAL
 AND DRAWINGS ALSO.
 3-WOOD COLUMN DETAILS: A)SPECIFY HOW
 MUCH EMBEDMENT FOR 1/2" ANCHOR BOLTS.
 B)CLEARLY IDENTIFY TOP CONNECTORS AND
 CLARIFY HOW ARE STRAPS USED RESISTING
 FOR LATERAL LOADS AND HOW ARE TO WOOD
 MEMBERS RESTING ON THE COLUMN BEING
 SUPPORTED BY THE METAL STRAPS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE SOIL TEST REPORT.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 **NOTE: NEED ORIGINAL SIGNED AND SEALED
 DRAWINGS AS REQUIRED BY THE ENGINEER.
 ALSO, NEED ADDITIONAL ENGINEERING FOR
 CERTAIN MOUNTING CONDITIONS. SEE SHEET
 4 OF 4 OF PRODUCT APPROVAL REPORT.
 6-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECIFICATIONS AND
 REVISE DETAIL AS REQUIRED.
 **NOTE: SPECIFY SIZE OF WASHER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-SPECIFY FIREBLOCKING @ STAIRS INCLUD'G
 AT TOP. SEE SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECIFICATIONS
 FOR FIREBLOCKING AT ALL CONCEALED
 SPACES. SEE SEC. 2305.1.4 FBC 2001.
 8-PROVIDE STRUCTURAL FRAMING DETAIL FOR
 INSTALLATION OF OVAL WINDOW. KEEP IN
 MIND THAT NEED 2X BUCK FOR ATTACHMENT
 OF WINDOW. SEC. 104.2.1.2 CITY AMENDM.
 9-REVISE STAIR KEY NOTE #1. HANDRAILS TO
 BE BET. 34" AND 38". SEC. 107.5.1 FBC.
 *NOTE: HANDRAILS & GUARDRAILS ARE NOT
 THE SAME.
 10-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED VALUES. OR PROVIDE
 ENGINEERING CALCULATIONS FOR DIFFERENT
 UPLIFT VALUES. NOTE: VALUES TO MATCH
 TYPE OF NAIL USED.
 11-SHOW NAILING ZONES ON ROOF PLAN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 12-ROOF PLAN: CLARIFY WHY THERE IS NOT
 BLOCKING SHOWN ON INTERIOR GABLE END.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 13-DETAIL R19: SPECIFY ALL FASTENERS.
 THERE IS NOT STRAP SPECIFIED ON ROOF
 PLAN. ALSO, PROVIDE COMPLETE SPECS
 SHOWING HOW IS TRUSS DESIGNED TO BE
 CONTINUOUS AT LATERAL SUPPORT. SEE
 SECTION 2117 AND 2313 FBC 2001.
 **NOTE: ALSO, PROVIDE COMPLETE DETAIL/
 SPECS FOR INTERIOR GABLE END SHOWING
 CONTINUITY AT LATERAL SUPPORT. SEC.
 2313 FBC 2001.
 14-PROVIDE FIRECUT REQUIREMENTS IN
 STRUCTURAL WALL SECTIONS. SEC. 2305.4