2002-08-13 00:00:00 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE TOTAL AREA LISTED ON SHEETS C1 & |
| A1 IS INCORRECT. CHECK THE ADDITION AND |
| CORRECT. |
| |
| 3)ONE HOUR RATED GLASS BLOCK IS REQUIRED |
| AT THE ZERO LOT LINE. PROVIDE UL |
| SPECIFICATIONS FOR A ONE HOUR FIRE RATED |
| GLASS BLOCK ASSEMBLY. THE GLASS BLOCK IS |
| ALSO LOCATED IN A HAZARDOUS LOCATION AND |
| MUST COMPLY WITH FBC 2405.2.2 AND HAVE A |
| MINIMUM UNIFORM FACE THICKNESS OF 0.25". |
| PLEASE SUBMIT MANUFACTURER'S SPECS. THAT |
| INDICATE FACE THICKNESS OF GLASS BLOCK. |
| |
| 4)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE THIS ON THE PLANS. |
| |
| 5) PLEASE CHANGE NOTE 6 ON A-2 TO REFER |
| TO THE 2001 FLORIDA PLUMBING CODE. |
| |
| 6) NUMBER 14 UNDER SECTION AND DETAILS |
| ON SHEET A-5 INDICATES 3"X24" SCREEN |
| VENTS AND THE SOFFIT VENT CALCS ON A-3 |
| LIST 6"X24" VENTS. PLEASE CLARIFY. |
| |
| 7) NOTE 3 ON S-2 IS FOR A 110 MPH WIND |
| VELOCITY AND THE CITY OF WPB IS LOCATED |
| IN A 140 MPH WIND ZONE. PLEASE CORRECT. |
| |
| 8) THE FOUNDATION THICKNESS IS SHOWN ON |
| THE SECTIONS ON A-5 AS 18". THE FOOTING |
| SCHEDULE ON S-2 LISTS IT AS 16". PLEASE |
| CLARIFY. |
| |
| 9) SHEET S-2 HAS A TAG FOR F14, WHICH IS |
| FOR A STEEL COLUMN AND SHOULD BE F16. |
| |
| 10) ON SHEET S-2, THERE IS A F5 TAG, |
| HOWEVER, THERE IS NO F5 SECTION GIVEN. |
| |
| 11) PROVIDE SOIL BEARING TEST PER FBC |
| SECTION 1804.2.2. |
| |
| 12) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SINGLE HUNG WINDOWS (COVER SHEET DOES |
| NOT BELONG WITH THE OTHER PAGES, WHICH |
| ARE EXPIRED) |
| - STRUCTURAL MULLIONS (EXPIRED) |
| |
| 13) STORM PANELS: THERE IS NO |
| INSTALLATION SCHEDULE. THE OPENING SIZES |
| ON THE KEY PLAN DO NOT ALL CORRESPOND |
| WITH THOSE ON THE PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |