Date |
Text |
2002-07-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) SHT 3.1 REST ROOM # 107. PER 11-4-1-3 |
| (11), EACH PUBLIC & COMMON TOILET ROOM |
| SHALL COMPLY WITH 11-4.2.22. OTHER TOI- |
| LET ROOMS PROVIDED FOR USE OF OCCUPANTS |
| OF SPECIFIC SPACES, (I.E., A PRIVATE |
| TOILET ROOM FOR THE OCCUPANT OF A PRIV- |
| ATE OFFICE) SHALL BE ADAPTABLE. SHOW |
| BACKING FOR GRAB BARS & SHR SEAT, AND |
| LOCATION FOR CONTROLS. ALSO GRAB BARS |
| FOR W/C. |
| 2) SHT P.1 PLUMBING NOTES #1 SUBMIT MAN- |
| UFACTURE INFORMATION FOR PRODUCT APPROV- |
| AL FOR STEAM UNIT. SHOW PAN DRAIN LINE |
| & T/P RELIEF VALVE DISCHARGE LINE AND |
| LOCATION OF TERMINATION FOR EACH. SEE |
| NOTE FOR PLENUM RATING REQUIRED FOR ALL |
| MATERIALS IN CEILING. |
| 3) SHTS P.1 & P.2 WATER HEATER DETAIL/ |
| PLUMBING FIXTURE SCHEDULE, FUNNEL FLOOR |
| DRAINS NOT APPROVED. ALL INDIRECT WASTE |
| SHALL DRAIN INTO A FLOOR SINK. 802.3 |
| 4) SHTS P.1 & P.2 WET VENT FOR TOILET |
| ROOM #109, ONLY FIXTURES WITHIN THE BATH |
| ROOM GROUP SHALL CONNECT TO THE WET-VENT |
| HORIZONTAL BRANCH DRAIN. CAFETERIA SINK |
| SHALL DISCHARGE DOWNSTREAM OF WET VENT. |
| 909.1 |
| 5) SHT P.2 WATER RISER, WATER HAMMER |
| ARRESTORS ARE REQUIRED AT QUICK CLOSING |
| VALVES, (W/M - DISHWASHER - ICE MAKER). |
| PLEASE SHOW W.H.A.'S AT CAFETERIS SINK. |
| 6) SUBMIT DETAIL FOR HDCP SHOWER. SHOW |
| COMPLIANCE WITH 11-4.21 AND ALL SUB SEC- |
| TIONS. |
| 7) SUBMIT RISER FOR CONDENSATE. SHOW |
| TERMINATION. IF TIED INTO STORM OR DRY- |
| WELL, A RELIEF VENT IS REQUIRED. IF |
| DRAINING ON TO GROUND, MINIMUM OF 12" |
| FROM BLDG REQUIRED. FBC 1503.4.4 |
| 8) SUBMIT MANUFACTURE INFORMATION FOR |
| INSTA-HOT. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |